2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable
- Voltage Rating(Uo/U)(Um) 36/60kV (72.5kV)
Construction
Conductor
Conductor Screen
Insulation
Insulation Screen
Wrapping
Metallic Screen
Sheath
Sheath Colour
Manufacturer Standard
Tape
Application
Technical Specifications
| No. Of Cores |
NOMINAL CROSS SECTIONAL AREA mm² |
INSULATION mm |
METALLIC SCREEN |
NOMINAL WEIGHT kg/km |
MAXIMUM PULLING FORCE kN |
||
| Nominal Thickness |
Nominal Diameter Over |
Nominal Cross Section mm² |
Nominal Diameter Over mm |
||||
| 1 | 120RM | 10.0 | 34.0 | 35 | 37.8 | 2670 | 6.0 |
| 1 | 150RM | 10.0 | 35.6 | 35 | 39.4 | 2980 | 7.5 |
| 1 | 185RM | 10.0 | 37.0 | 35 | 40.8 | 3370 | 9.3 |
| 1 | 240RM | 10.0 | 39.7 | 35 | 43.5 | 3990 | 12.0 |
| 1 | 300RM | 10.0 | 41.7 | 35 | 45.5 | 4650 | 15.0 |
| 1 | 400RM | 10.0 | 42.5 | 35 | 46.7 | 5660 | 20.0 |
| 1 | 500RM | 10.0 | 48.0 | 35 | 52.2 | 6780 | 25.0 |
| 1 | 630RM | 10.0 | 52.1 | 35 | 56.3 | 8220 | 31.5 |
| 1 | 800RM | 10.0 | 56.5 | 35 | 60.7 | 9980 | 40.0 |
| 1 | 1000RM | 10.0 | 60.5 | 35 | 65.1 | 12140 | 50.0 |
| 1 | 1200RMS | 10.0 | 65.8 | 50 | 70.4 | 14500 | 60.0 |
| 1 | 1400RMS | 10.0 | 70.0 | 50 | 74.6 | 16560 | 70.0 |
| 1 | 1600RMS | 10.0 | 73.8 | 50 | 78.4 | 18580 | 80.0 |
| 1 | 1800RMS | 10.0 | 77.4 | 50 | 82.0 | 20930 | 90.0 |
| 1 | 2000RMS | 10.0 | 78.8 | 50 | 83.4 | 22490 | 100.0 |
| 1 | 2500RMS | 85.2 | 50 | 90.2 | 27450 | 100.0 | |
| 1 | 3000RMS | 93.6 | 50 | 98.6 | 33750 | 100.0 | |
Quality Control
Raw Material Test
Raw material testing is the first quality assurance step for the 2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable. Conductors are tested for electrical conductivity, tensile strength, elongation, and dimensional accuracy to ensure efficient current transmission and mechanical reliability. The aluminum laminate (FL) moisture barrier is inspected for thickness consistency, bonding strength, corrosion resistance, and longitudinal water-blocking performance. MDPE sheath materials undergo tensile strength, elongation, abrasion resistance, environmental stress crack resistance, and UV resistance testing. All raw materials used in the 2XS(FL)2Y cable are fully traceable and documented. Only materials that meet all technical and quality requirements are approved for production, ensuring a reliable foundation for long-term high-voltage performance.
Process inspection
Process inspection ensures consistent manufacturing quality of the 2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable throughout all production stages. During conductor stranding and compaction, inspections verify strand structure, conductor diameter, surface smoothness, and concentricity. Application of the aluminum laminate screen is inspected to ensure correct overlap, bonding quality, and continuous moisture barrier integrity. MDPE sheath extrusion is monitored for thickness uniformity, adhesion, and surface finish. Spark testing, dimensional checks, and in-process electrical inspections are performed throughout production. All process data is recorded and reviewed. Any deviation triggers immediate corrective action to maintain stable and consistent quality.
Finished Product
Finished product testing verifies the overall quality and safety of the 2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable before delivery. Electrical tests include conductor resistance measurement, partial discharge testing, and AC voltage withstand testing according to IEC standards for 72.5kV systems. Thermal tests confirm insulation stability under continuous operating temperatures. Mechanical tests assess tensile strength, bending performance, and impact resistance to ensure installation reliability. Water penetration and sheath integrity tests verify moisture protection performance. Dimensional inspections confirm conductor size, insulation thickness, screen structure, and sheath thickness. Final visual inspection ensures correct marking, smooth surface finish, and defect-free construction.
Application
Technical Advantages
Product Packaging
Related Products
FAQ From Customers
-
What are the advantages of power cables and overhead lines?(1) Reliable operation, because it is installed in a hidden place such as underground, it is less damaged by external forces, has less chance of failure, and the power supply is safe, and it will not cause harm to people; (2) The maintenance workload is small and frequent inspections are not required; (3) No need to erect towers; (4) Help improve power factor.
-
Which aspects should be considered when choosing the cross section of a power cable?(1) The long-term allowable working current of the cable; (2) Thermal stability once short circuited; (3) The voltage drop on the line cannot exceed the allowable working range.
-
What are the measures for cable fire prevention?(1) Use flame-retardant cables; (2) Use fireproof cable tray; (3) Use fireproof paint; (4) Fire partition walls and fire baffles are installed at cable tunnels, mezzanine exits, etc.; (5) Overhead cables should avoid oil pipelines and explosion-proof doors, otherwise local pipes or heat insulation and fire prevention measures should be taken.
-
What should be paid attention to during the transportation and handling of cables?(1) During transportation, loading and unloading, cables and cable reels should not be damaged. It is strictly forbidden to push the cable reels directly from the vehicle. Generally, cables should not be transported and stored flat. (2) Before transporting or rolling the cable reel, ensure that the cable reel is firm, the cable is wound tightly, the oil pipe between the oil-filled cable and the pressure oil tank should be fixed without damage, the pressure oil tank should be firm, and the pressure indication should meet the requirements.
-
What inspections should be carried out for the acceptance of cable lines?(1) The cable specifications should meet the regulations, the arrangement should be neat, no damage, and the signs should be complete, correct and clear; (2) The fixed bending radius of the cable, the related distance and the wiring of the metal sheath of the single-core power cable should meet the requirements; (3) The cable terminal and the middle head should not leak oil, and the installation should be firm. The oil pressure of the oil-filled cable and the meter setting should meet the requirements; (4) Good grounding; (5) The color of the cable terminal is correct, and the metal parts such as the bracket are completely painted; (6) There should be no debris in the cable trench, tunnel, and bridge, and the cover should be complete.