2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable
2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable

2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable

The 2XS(FL)2Y MDPE High Voltage Power Cable is a single-core aluminum conductor cable with XLPE insulation and an MDPE sheath, rated 36/60 (72.5) kV. Designed for high-voltage power transmission, it complies with IEC 60840 standards, delivering excellent electrical performance, robust mechanical protection, and outstanding water resistance for demanding applications. Its construction features a copper conductor, semi-conductive conductor screen, XLPE insulation, semi-conductive insulation screen, semi-conductive water swelling tape, copper wire metallic screen, longitudinal aluminum tape with PE copolymer coating, and a durable MDPE sheath. The water-blocking tape prevents water propagation inside the cable, ensuring reliable operation in power stations, industrial facilities, and distribution networks. This cable is suitable for distribution networks, connections to generation units, and industrial plants, with installation options including underground, underwater, outdoor, indoor, and cable ducts.
Voltage Rating(Uo/U)(Um) 36/60kV (72.5kV)
Construction
Technical Specifications
Quality Control
Application

Construction

2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable Constrution
2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable

Conductor

Copper conductor (optional watertightness – WTC)

Conductor Screen

Semi-conductive screen extruded on the phase conductor

Insulation

XLPE (Cross-Linked Polyethylene)

Insulation Screen

Semi-conductive screen extruded on insulation

Wrapping

Semi-conductive water swelling tape

Metallic Screen

Copper wires and equalising tape

Sheath

MDPE (Medium Density Polyethylene) Optional —semi-conductive layer

Sheath Colour

Black

Manufacturer Standard

IEC 60840

Tape

Longitudinally applied aluminium tape coated with PE copolymer

Application

2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable is suitable for distribution networks and connections to generation units and industrial plants, designed for installation underground, underwater, outdoors, indoors, and in cable ducts.

Technical Specifications

2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable
2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable
No. Of Cores

NOMINAL CROSS

SECTIONAL AREA

mm²

INSULATION
mm
METALLIC SCREEN

NOMINAL

WEIGHT

kg/km

MAXIMUM PULLING

FORCE

kN

Nominal Thickness

Nominal Diameter

Over

Nominal Cross

Section

mm²

Nominal Diameter

Over

mm

1 120RM 10.0 34.0 35 37.8 2670 6.0
1 150RM 10.0 35.6 35 39.4 2980 7.5
1 185RM 10.0 37.0 35 40.8 3370 9.3
1 240RM 10.0 39.7 35 43.5 3990 12.0
1 300RM 10.0 41.7 35 45.5 4650 15.0
1 400RM 10.0 42.5 35 46.7 5660 20.0
1 500RM 10.0 48.0 35 52.2 6780 25.0
1 630RM 10.0 52.1 35 56.3 8220 31.5
1 800RM 10.0 56.5 35 60.7 9980 40.0
1 1000RM 10.0 60.5 35 65.1 12140 50.0
1 1200RMS 10.0 65.8 50 70.4 14500 60.0
1 1400RMS 10.0 70.0 50 74.6 16560 70.0
1 1600RMS 10.0 73.8 50 78.4 18580 80.0
1 1800RMS 10.0 77.4 50 82.0 20930 90.0
1 2000RMS 10.0 78.8 50 83.4 22490 100.0
1 2500RMS   85.2 50 90.2 27450 100.0
1 3000RMS   93.6 50 98.6 33750 100.0

Quality Control

2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable
Raw Material Test

Raw Material Test

Raw material testing is the first quality assurance step for the 2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable. Conductors are tested for electrical conductivity, tensile strength, elongation, and dimensional accuracy to ensure efficient current transmission and mechanical reliability. The aluminum laminate (FL) moisture barrier is inspected for thickness consistency, bonding strength, corrosion resistance, and longitudinal water-blocking performance. MDPE sheath materials undergo tensile strength, elongation, abrasion resistance, environmental stress crack resistance, and UV resistance testing. All raw materials used in the 2XS(FL)2Y cable are fully traceable and documented. Only materials that meet all technical and quality requirements are approved for production, ensuring a reliable foundation for long-term high-voltage performance.

Process inspection

Process inspection

Process inspection ensures consistent manufacturing quality of the 2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable throughout all production stages. During conductor stranding and compaction, inspections verify strand structure, conductor diameter, surface smoothness, and concentricity. Application of the aluminum laminate screen is inspected to ensure correct overlap, bonding quality, and continuous moisture barrier integrity. MDPE sheath extrusion is monitored for thickness uniformity, adhesion, and surface finish. Spark testing, dimensional checks, and in-process electrical inspections are performed throughout production. All process data is recorded and reviewed. Any deviation triggers immediate corrective action to maintain stable and consistent quality.

Finished Product

Finished Product

Finished product testing verifies the overall quality and safety of the 2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable before delivery. Electrical tests include conductor resistance measurement, partial discharge testing, and AC voltage withstand testing according to IEC standards for 72.5kV systems. Thermal tests confirm insulation stability under continuous operating temperatures. Mechanical tests assess tensile strength, bending performance, and impact resistance to ensure installation reliability. Water penetration and sheath integrity tests verify moisture protection performance. Dimensional inspections confirm conductor size, insulation thickness, screen structure, and sheath thickness. Final visual inspection ensures correct marking, smooth surface finish, and defect-free construction.

Application

2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable is suitable for distribution networks and connections to generation units and industrial plants, designed for installation underground, underwater, outdoors, indoors, and in cable ducts.

Technical Advantages

● 30+ years of manufacturing experience
● ISO and UL certified production
● Customized cable and transformer solutions

Product Packaging

Wires and Cables packaging (1)
Wires and Cables packaging (1)
Wires and Cables packaging (2)
Wires and Cables packaging (2)
Wires and Cables packaging (3)
Wires and Cables packaging (3)
Wires and Cables packaging (4)
Wires and Cables packaging (4)
Wires and Cables packaging (5)
Wires and Cables packaging (5)
Wires and Cables packaging (6)
Wires and Cables packaging (6)
Wires and Cables packaging (7)
Wires and Cables packaging (7)
Wires and Cables packaging (8)
Wires and Cables packaging (8)

Related Products

FAQ From Customers

What are the advantages of power cables and overhead lines?
(1) Reliable operation, because it is installed in a hidden place such as underground, it is less damaged by external forces, has less chance of failure, and the power supply is safe, and it will not cause harm to people;
(2) The maintenance workload is small and frequent inspections are not required;
(3) No need to erect towers;
(4) Help improve power factor.
Which aspects should be considered when choosing the cross section of a power cable?
(1) The long-term allowable working current of the cable;
(2) Thermal stability once short circuited;
(3) The voltage drop on the line cannot exceed the allowable working range.
What are the measures for cable fire prevention?
(1) Use flame-retardant cables;
(2) Use fireproof cable tray;
(3) Use fireproof paint;
(4) Fire partition walls and fire baffles are installed at cable tunnels, mezzanine exits, etc.;
(5) Overhead cables should avoid oil pipelines and explosion-proof doors, otherwise local pipes or heat insulation and fire prevention measures should be taken.
What should be paid attention to during the transportation and handling of cables?
(1) During transportation, loading and unloading, cables and cable reels should not be damaged. It is strictly forbidden to push the cable reels directly from the vehicle. Generally, cables should not be transported and stored flat.
(2) Before transporting or rolling the cable reel, ensure that the cable reel is firm, the cable is wound tightly, the oil pipe between the oil-filled cable and the pressure oil tank should be fixed without damage, the pressure oil tank should be firm, and the pressure indication should meet the requirements.
What inspections should be carried out for the acceptance of cable lines?
(1) The cable specifications should meet the regulations, the arrangement should be neat, no damage, and the signs should be complete, correct and clear;
(2) The fixed bending radius of the cable, the related distance and the wiring of the metal sheath of the single-core power cable should meet the requirements;
(3) The cable terminal and the middle head should not leak oil, and the installation should be firm. The oil pressure of the oil-filled cable and the meter setting should meet the requirements;
(4) Good grounding;
(5) The color of the cable terminal is correct, and the metal parts such as the bracket are completely painted;
(6) There should be no debris in the cable trench, tunnel, and bridge, and the cover should be complete.

Welcome your inquiry