3/0 Suffolk Aluminum Conductor Quadruplex Overhead Service Drop Cable
3/0 Suffolk Aluminum Conductor Quadruplex Overhead Service Drop Cable

3/0 Suffolk Aluminum Conductor Quadruplex Overhead Service Drop Cable

3/0 Suffolk Aluminum Conductor Quadruplex Overhead Service Drop Cable is specifically designed to deliver three-phase power from pole-mounted transformers to customer premises in residential, commercial, and light industrial applications. With a 600-volt phase-to-phase voltage rating and a durable build, this cable ensures long-term performance in outdoor environments. The conductors are made of 1350-H19 aluminum, either stranded or compressed, and are insulated with UV-resistant black cross-linked polyethylene (XLP) for superior thermal endurance, rated up to 90°C. For standard polyethylene (PE) insulation, the conductor temperature rating is 75°C. The cable also includes a bare ACSR (Aluminum Conductor Steel Reinforced) messenger, providing mechanical support during overhead installation. Optional messenger types such as AAC or 6201 alloy are available to suit different utility standards or corrosion resistance needs.
Construction
Technical Specifications
Quality Control
Application

Construction

3/0 Suffolk Aluminum Conductor Quadruplex Overhead Service Drop Cable Construction
3/0 Suffolk Aluminum Conductor Quadruplex Overhead Service Drop Cable Construction

Standard

• ASTM B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
• ASTM B-231 Aluminum Conductors, Concentric-Lay-Stranded.
• ASTM B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
• ASTM B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
• ICEA S-76-474-Neutral-supported Power Cable Assemblies With Weather-Resistant Extruded Insulation Rated 600Volts

Phase Conductor

Strand or Compressed 1350-H19 Series Aluminum Conductor.

Neutral(Messenger )Conductor

Bare ACSR messenger. Optional constructions include a messenger of AAC or 6201 alloy.

Insulation

Black Cross Linked Polyethylene (XLP) Insulation.

Application

3/0 suffolk conductor quadruplex overhead service drop cable used to supply 3-phase power, usually from a pole mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts phase to phase or less and at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for cross linked polyethylene (XLP) insulated conductors

Application Type

3/0 suffolk aluminum quadruplex, 3/0 suffolk overhead service drop, 3/0 suffolk three phase cable, 3/0 suffolk 3 phase cable, 3/0 suffolk 3 phase power cable, 3/0 suffolk 3 phase extension cord, 3/0 suffolk 3 phase aluminum cable, 3/0 suffolk 3 phase electrical cable, 3/0 suffolk three phase power cable, 3/0 suffolk quadruplex wire, 3/0 suffolk quadruplex overhead wire, 3/0 suffolk overhead service entrance cable.

Features

1. Suitable for overhead service drops in residential, commercial, or light industrial use
2. Rated for 600V or less, 3-phase systems
3. XLP insulation ensures heat and weather resistance
4. Built to meet ASTM B-230, B-231, B-232, B-399, and ICEA S-76-474 standards
5. Strong and reliable ACSR neutral messenger for mechanical support
6. Flexible construction options: AAC or 6201 alloy messengers available

Technical Specifications

3/0 Suffolk Aluminum Conductor Quadruplex Overhead Service Drop Cable
3/0 Suffolk Aluminum Conductor Quadruplex Overhead Service Drop Cable
Rated voltage kV 0.6/1
Test voltage Veff kV/Hz 4/50
Laying temperature °C min. -5
Operating temperature °C -30 ~ +90
Conductor temperature °C max. +90
Short-circuit temperature °C/s max. +250 /5
Bending radius (min.) mm 20 × Ø of cable

Quality Control

3/0 Suffolk Aluminum Conductor Quadruplex Overhead Service Drop Cable
3/0 Suffolk Aluminum Conductor Quadruplex Service Drop Cable Material Test

Raw Material Test

NPC has always chosen raw material suppliers who have a good reputation, possess stable supply capabilities and have passed international quality system certifications (such as ISO 9001). And establish a long-term cooperative relationship with it, forming a stable and reliable raw material supply chain.
We will ensure that all raw materials are subject to strict inspection procedures upon entry to the factory, and can only be stored in the warehouse after they have been confirmed to meet the standards.

3/0 Suffolk Aluminum Conductor Quadruplex Service Drop Cable  Process inspection

Process inspection

NPC has strict quality control procedures for each process in the cable production process.
Process documents: Develop detailed process flow and operation instructions to clarify the operating specifications and quality standards of each process.
Equipment calibration: Regularly calibrate key equipment such as wire drawing machines, stranding machines, extruders, and diameter gauges to ensure that the accuracy meets the requirements.
First piece confirmation: Before each batch of production, the first piece is trial-produced to confirm that the process parameters, product dimensions, electrical performance, etc. meet the standards before mass production can be carried out.

3/0 Suffolk Aluminum Conductor Quadruplex Service Drop Cable  Finished Product

Finished Product

Inspectors conduct ex-factory inspections on cables according to relevant standards and corresponding product inspection specifications to ensure that each ex-factory product complies with the process regulations.

Application

3/0 suffolk conductor quadruplex overhead service drop cable used to supply 3-phase power, usually from a pole mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts phase to phase or less and at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for cross linked polyethylene (XLP) insulated conductors

Technical Advantages

● 30+ years of manufacturing experience
● ISO and UL certified production
● Customized cable and transformer solutions

Product Packaging

Wires and Cables packaging (1)
Wires and Cables packaging (1)
Wires and Cables packaging (2)
Wires and Cables packaging (2)
Wires and Cables packaging (3)
Wires and Cables packaging (3)
Wires and Cables packaging (4)
Wires and Cables packaging (4)
Wires and Cables packaging (5)
Wires and Cables packaging (5)
Wires and Cables packaging (6)
Wires and Cables packaging (6)
Wires and Cables packaging (7)
Wires and Cables packaging (7)
Wires and Cables packaging (8)
Wires and Cables packaging (8)

Related Products

FAQ From Customers

What are the advantages of power cables and overhead lines?
(1) Reliable operation, because it is installed in a hidden place such as underground, it is less damaged by external forces, has less chance of failure, and the power supply is safe, and it will not cause harm to people;
(2) The maintenance workload is small and frequent inspections are not required;
(3) No need to erect towers;
(4) Help improve power factor.
Which aspects should be considered when choosing the cross section of a power cable?
(1) The long-term allowable working current of the cable;
(2) Thermal stability once short circuited;
(3) The voltage drop on the line cannot exceed the allowable working range.
What are the measures for cable fire prevention?
(1) Use flame-retardant cables;
(2) Use fireproof cable tray;
(3) Use fireproof paint;
(4) Fire partition walls and fire baffles are installed at cable tunnels, mezzanine exits, etc.;
(5) Overhead cables should avoid oil pipelines and explosion-proof doors, otherwise local pipes or heat insulation and fire prevention measures should be taken.
What should be paid attention to during the transportation and handling of cables?
(1) During transportation, loading and unloading, cables and cable reels should not be damaged. It is strictly forbidden to push the cable reels directly from the vehicle. Generally, cables should not be transported and stored flat.
(2) Before transporting or rolling the cable reel, ensure that the cable reel is firm, the cable is wound tightly, the oil pipe between the oil-filled cable and the pressure oil tank should be fixed without damage, the pressure oil tank should be firm, and the pressure indication should meet the requirements.
What inspections should be carried out for the acceptance of cable lines?
(1) The cable specifications should meet the regulations, the arrangement should be neat, no damage, and the signs should be complete, correct and clear;
(2) The fixed bending radius of the cable, the related distance and the wiring of the metal sheath of the single-core power cable should meet the requirements;
(3) The cable terminal and the middle head should not leak oil, and the installation should be firm. The oil pressure of the oil-filled cable and the meter setting should meet the requirements;
(4) Good grounding;
(5) The color of the cable terminal is correct, and the metal parts such as the bracket are completely painted;
(6) There should be no debris in the cable trench, tunnel, and bridge, and the cover should be complete.