x
NTSCGECECWOU 8.7/15kV and 12/20kV Cable
NTSCGECECWOU 8.7/15kV and 12/20kV Cable

NTSCGECECWOU 8.7/15kV and 12/20kV Cable

NTSCGECECWOU 8.7/15kV and 12/20kV cable is a flexible medium voltage power cable manufactured according to DIN VDE 0250 standards, engineered for heavy-duty energy supply in mining, tunneling, and mobile equipment applications. Featuring Class 5 tinned copper conductors, EPR insulation, a halogen-free flame-retardant sheath, and concentric copper conductors for EMC protection, it ensures outstanding mechanical strength, oil and moisture resistance, and fire safety. Designed for reeling drum systems and mobile machinery, it is ideal for both indoor and outdoor use in harsh, demanding environments.
Voltage Rating Uo/U 8.7/15kV | 12/20kV
Test Voltage 8.7/15kV: 24kV
12/20kV: 29kV
Temperature Rating Fixed: -40°C to +80°C
Flexed: -25°C to +80°C
Minimum Bending Radius Fixed: 6 x overall diameter
Flexed: 10 x overall diameter
Maximum Torsional Stress ±25°/m
Construction
Technical Specifications
Quality Control
Application

Construction

NTSCGECECWOU 8.7/15kV and 12/20kV Cable Constrution
NTSCGECECWOU 8.7/15kV and 12/20kV Cable

Phase Conductor

Class 5 tinned copper conductor

Insulation

Rubber compound

Protective Earth Conductor

Individual copper wire screen

Control Conductor

Class 5 tinned copper

Central Filler

Semi-conductive compound on a polyester textile support

Inner Sheath

Rubber Compound

Monitoring Conductor

Copper wire screen over the inner sheath

Outer Sheath

Rubber Compound

Sheath Colour

Red

Manufacturer Standard

VDE 0250 Part 813, VDE 0295, EN 60228

Flame Retardant

IEC/EN 60332-1-2

Semi-Conductive Layers

Semi-conductive tape over the conductor and inner and outer
Semi-conductive rubber layer on the insulation

Application

NTSCGECECWOU 8.7/15kV and 12/20kV cable is used for power supply in tunnel boring machines with reeling drum systems, as well as other demanding tunnel construction applications. It is suitable for both indoor and outdoor installations, offering flexibility and durability in harsh environments.

Technical Specifications

NTSCGECECWOU 8.7/15kV and 12/20kV Cable
NTSCGECECWOU Cable 8.7/15kV
NTSCGECECWOU Cable 12/20kV

No. Of Cores
(PHASE+EARH +

CONTROL+UL)

Nominal Cross Sectional Area
mm²

CONDUCTOR

DIAMETER

MINIMUM OVERALL

DIAMETER

MAXIMUM OVERALL

DIAMETER

MAXIMUM

TENSILE LOAD

NOMINAL

WEIGHT

Phase N

Conductor

Earth

Conductor

Control

Conductor

mm mm mm N kg/km
3+3+3+UL 25 25/3E 2.5ST 6.8 48 51.5 1125 3590
3+3+3+UL 35 25/3E 2.5ST 7.8 49.5 53.1 1575 3990
3+3+3+UL 50 25/3E 2.5ST 9.4 54.4 58.2 2250 4880
3+3+3+UL 70 35/3E 2.5ST 11.2 58.2 62.2 3150 5950
3+3+3+UL 95 50/3E 2.5ST 12.7 61.4 65.7 4275 7030
3+3+3+UL 120 70/3E 2.5ST 14.4 67.4 71.9 5400 8690

No. Of Cores
(PHASE+EARH +

CONTROL+UL)

Nominal Cross Sectional Area
mm²

CONDUCTOR

DIAMETER

MINIMUM OVERALL

DIAMETER

MAXIMUM OVERALL

DIAMETER

MAXIMUM

TENSILE LOAD

NOMINAL

WEIGHT

Phase N

Conductor

Earth

Conductor

Control

Conductor

mm mm mm N kg/km
3+3+3+UL 25 25/3E 2.5ST 6.8 50.5 54.1 1125 3860
3+3+3+UL 35 25/3E 2.5ST 7.8 52.3 56 1575 4260
3+3+3+UL 50 25/3E 2.5ST 9.4 57.5 61.4 2250 5190
3+3+3+UL 70 35/3E 2.5ST 11.2 61 65.3 3150 6280
3+3+3+UL 95 50/3E 2.5ST 12.7 66.4 70.9 4275 7640
3+3+3+UL 120 70/3E 2.5ST 14.4 70.5 75.2 5400 9050

Quality Control

NTSCGECECWOU 8.7/15kV and 12/20kV Cable
NTSCGECECWOU Cable Raw Material Test

Raw Material Test

Raw Material Test for (N)TSCGECECWOU 8.7/15kV & 12/20kV Cable prioritizes high-voltage mining quality. Steps include: Certification Verification: Tinned copper, EPR, and rubber sheath meet VDE 0250/IEC standards. Conductor Testing: Tensile, elongation, conductivity, tin coating analysis. Insulation/Screen Evaluation: EPR dielectric/thermal properties; semi-conductive adhesion/resistivity. Sheath & Braid Checks: Abrasion/oil/flame resistance, braid coverage/strength. Control/Monitoring Validation: Conductor properties confirmed. Batch Rejection: Non-compliant quarantined. Approved materials ensure the (N)TSCGECECWOU 8.7/15kV & 12/20kV Cable's flexibility and MV reliability.

NTSCGECECWOU Cable Process inspection

Process inspection

Process Inspection for (N)TSCGECECWOU 8.7/15kV & 12/20kV Cable enforces manufacturing precision. The procedure features: Stranding Control: Uniform tinned copper phases/control/monitoring. Extrusion Monitoring: Semi-conductive screens, EPR insulation with defect detection. Screening & Assembly: Precise braid and conductor integration. Real-Time Checks: Resistance, integrity, diameter monitoring. Optimization: Extrusion parameters adjusted. Correction: Immediate fixes. This guarantees the (N)TSCGECECWOU 8.7/15kV & 12/20kV Cable excels in MV electrical and mechanical performance.

NTSCGECECWOU Cable Finished Product

Finished Product

Finished Product Test validates the (N)TSCGECECWOU 8.7/15kV & 12/20kV Cable for deployment. Steps include: Inspection: Visual/dimensional/marking verification. Electrical: Resistance, insulation, withstand (24–29kV), partial discharge. Mechanical: Bending, tensile, abrasion resistance. Performance: Oil/flame/thermal aging checks.= Validation: Voltage rating and short-circuit capability confirmed. Release: Only passing (N)TSCGECECWOU 8.7/15kV & 12/20kV Cable approved for dependable mining/tunneling MV use.

Application

The (N)TSCGECECWOU 8.7/15kV and 12/20kV Cable is perfect for underground/open-pit mining trailing/reeling systems, tunnel boring machines, heavy excavators, conveyor power feeds, mobile substations, and switchgear connections requiring flexible, screened, oil/abrasion-resistant MV cable with control/monitoring in high-mechanical-stress environments.

Technical Advantages

● 30+ years of manufacturing experience
● ISO and UL certified production
● Customized cable and transformer solutions

Product Packaging

Wires and Cables packaging (1)
Wires and Cables packaging (1)
Wires and Cables packaging (2)
Wires and Cables packaging (2)
Wires and Cables packaging (3)
Wires and Cables packaging (3)
Wires and Cables packaging (4)
Wires and Cables packaging (4)
Wires and Cables packaging (5)
Wires and Cables packaging (5)
Wires and Cables packaging (6)
Wires and Cables packaging (6)
Wires and Cables packaging (7)
Wires and Cables packaging (7)
Wires and Cables packaging (8)
Wires and Cables packaging (8)

Related Products

FAQ From Customers

What are the advantages of power cables and overhead lines?
(1) Reliable operation, because it is installed in a hidden place such as underground, it is less damaged by external forces, has less chance of failure, and the power supply is safe, and it will not cause harm to people;
(2) The maintenance workload is small and frequent inspections are not required;
(3) No need to erect towers;
(4) Help improve power factor.
Which aspects should be considered when choosing the cross section of a power cable?
(1) The long-term allowable working current of the cable;
(2) Thermal stability once short circuited;
(3) The voltage drop on the line cannot exceed the allowable working range.
What are the measures for cable fire prevention?
(1) Use flame-retardant cables;
(2) Use fireproof cable tray;
(3) Use fireproof paint;
(4) Fire partition walls and fire baffles are installed at cable tunnels, mezzanine exits, etc.;
(5) Overhead cables should avoid oil pipelines and explosion-proof doors, otherwise local pipes or heat insulation and fire prevention measures should be taken.
What should be paid attention to during the transportation and handling of cables?
(1) During transportation, loading and unloading, cables and cable reels should not be damaged. It is strictly forbidden to push the cable reels directly from the vehicle. Generally, cables should not be transported and stored flat.
(2) Before transporting or rolling the cable reel, ensure that the cable reel is firm, the cable is wound tightly, the oil pipe between the oil-filled cable and the pressure oil tank should be fixed without damage, the pressure oil tank should be firm, and the pressure indication should meet the requirements.
What inspections should be carried out for the acceptance of cable lines?
(1) The cable specifications should meet the regulations, the arrangement should be neat, no damage, and the signs should be complete, correct and clear;
(2) The fixed bending radius of the cable, the related distance and the wiring of the metal sheath of the single-core power cable should meet the requirements;
(3) The cable terminal and the middle head should not leak oil, and the installation should be firm. The oil pressure of the oil-filled cable and the meter setting should meet the requirements;
(4) Good grounding;
(5) The color of the cable terminal is correct, and the metal parts such as the bracket are completely painted;
(6) There should be no debris in the cable trench, tunnel, and bridge, and the cover should be complete.