x
High Voltage / 2XS(FL)2Y, A2XS(FL)2Y 110kV Power Cable
High Voltage / 2XS(FL)2Y, A2XS(FL)2Y 110kV Power Cable

High Voltage / 2XS(FL)2Y, A2XS(FL)2Y 110kV Power Cable

2XS(FL)2Y / A2XS(FL)2Y 110kV High Voltage Power Cable is a longitudinally watertight, XLPE-insulated cable designed for primary power distribution up to 110kV (123kV highest). It features a Class 2 copper or aluminium conductor, extruded semi-conductive XLPE screens, and XLPE insulation applied via a three-layer co-extrusion process for superior electrical performance. A laminated aluminium or copper moisture barrier with copolymer coating provides excellent water and gas resistance, while HDPE oversheath ensures high abrasion resistance and flexibility. The copper wire screen with counter-helical copper tape offers optimal shielding, and water swellable tapes ensure longitudinal water blocking. Manufactured to IEC 60840, HRN HD 632, and IEC/EN 60228 standards, this cable is ideal for underground installations requiring high reliability and moisture protection.
Voltage Rating (Uo/U)(Um) 64/110kV (123kV)
Highest Network Voltage 123kV
Operating Temperature -30°C to +90°C
Short Circuit Temperature +250°C
Minimum Installation Temperature -20°C
Construction
Technical Specifications
Quality Control
Application

Construction

High Voltage / 2XS(FL)2Y, A2XS(FL)2Y 110kV Power CableConstrution
High Voltage / 2XS(FL)2Y, A2XS(FL)2Y 110kV Power Cable

Conductor

Class 2 copper or aluminium, compacted or segment

Insulation

XLPE (Cross-Linked Polyethylene)

Conductor Screen

Extruded semi-conductive XLPE (Cross-Linked Polyethylene)

Insulation Screen

Extruded Semi-conductive XLPE (Cross-Linked Polyethylene)

Separator

Water-swellable semi-conductive tape

Screen

Copper wire screen, with a counter helix of copper tape

Sheath

HDPE (High-Density Polyethylene) (To be specified at time of order. Other options available)

Sheath Colour

Black

Manufacturer Standard

IEC 60840, HRN HD 632, IEC/EN 60228

Moisture Barrier

Aluminium or Copper tape with copolymer

Application

The 2XS(FL)2Y and A2XS(FL)2Y 110kV high-voltage cables are suitable for primary distribution systems up to 110kV. Utilizing a three-layer co-extrusion process and featuring a moisture-proof foil structure, these cables offer excellent waterproofing and mechanical protection. Their high-density polyethylene jacket provides both abrasion resistance and flexibility, and can be customized to suit various engineering environments.

Technical Specifications

High Voltage / 2XS(FL)2Y, A2XS(FL)2Y 110kV Power Cable
2XS(FL)2Y Copper Conductor
A2XS(FL)2Y Aluminium Conductor

No. Of

Cores

NOMINAL CROSS

SECTIONAL AREA

mm²

ELECTRICAL

PROTECTION

mm²

NOMINAL DIAMETER

OF CONDUCTOR

mm

NOMINAL THICKNESS

OF INSULATION

mm

NOMINAL DIAMETER

OVER INSULATION

mm

NOMINAL OVERALL

DIAMETER

mm

NOMINAL

WEIGHT

kg/km

1 150 95 14.1 18 54.9 64.9 5035
1 185 95 15.7 17 54.5 64.5 5272
1 240 95 18 16 54.8 64.8 5742
1 300 95 20.3 15 55.1 65.1 6210
1 400 95 23 15 57.6 67.4 7208
1 500 95 26.5 15 61.3 71.7 8322
1 630 95 30.3 15 64.5 75.2 9886
1 800 95 36.9 15 71.8 82.6 12042

No. Of

Cores

NOMINAL CROSS

SECTIONAL AREA

mm²

ELECTRICAL

PROTECTION

mm²

NOMINAL DIAMETER

OF CONDUCTOR

mm

NOMINAL THICKNESS

OF INSULATION

mm

NOMINAL DIAMETER

OVER INSULATION

mm

NOMINAL OVERALL

DIAMETER

mm

NOMINAL

WEIGHT

kg/km

1 150 95 14.1 18 54.9 64.9 4128
1 185 95 15.7 17 54.5 64.5 4153
1 240 95 18 16 54.8 64.8 4283
1 300 95 20.3 15 55.1 65.1 4397
1 400 95 23 15 57.6 67.4 4880
1 500 95 26.5 15 61.3 71.7 5433
1 630 95 30.3 15 64.5 75.2 6064
1 800 95 36.9 15 71.8 82.6 7100
1 1000 95 37.9 15 72.8 84.7 7795
1 1200* 95 44 15 78 95.7 8350

Quality Control

High Voltage / 2XS(FL)2Y, A2XS(FL)2Y 110kV Power Cable
Raw Material Test

Raw Material Test

NPC has always chosen raw material suppliers who have a good reputation, possess stable supply capabilities and have passed international quality system certifications (such as ISO 9001). And establish a long-term cooperative relationship with it, forming a stable and reliable raw material supply chain.
We will ensure that all raw materials are subject to strict inspection procedures upon entry to the factory, and can only be stored in the warehouse after they have been confirmed to meet the standards.

Process inspection

Process inspection

NPC has strict quality control procedures for each process in the cable production process.
Process documents: Develop detailed process flow and operation instructions to clarify the operating specifications and quality standards of each process.
Equipment calibration: Regularly calibrate key equipment such as wire drawing machines, stranding machines, extruders, and diameter gauges to ensure that the accuracy meets the requirements.
First piece confirmation: Before each batch of production, the first piece is trial-produced to confirm that the process parameters, product dimensions, electrical performance, etc. meet the standards before mass production can be carried out.

Finished Product

Finished Product

Inspectors conduct ex-factory inspections on cables according to relevant standards and corresponding product inspection specifications to ensure that each ex-factory product complies with the process regulations.

Application

The 2XS(FL)2Y and A2XS(FL)2Y 110kV high-voltage cables are suitable for primary distribution systems up to 110kV. Utilizing a three-layer co-extrusion process and featuring a moisture-proof foil structure, these cables offer excellent waterproofing and mechanical protection.

Technical Advantages

● 30+ years of manufacturing experience
● ISO and UL certified production
● Customized cable and transformer solutions

Product Packaging

Wires and Cables packaging (1)
Wires and Cables packaging (1)
Wires and Cables packaging (2)
Wires and Cables packaging (2)
Wires and Cables packaging (3)
Wires and Cables packaging (3)
Wires and Cables packaging (4)
Wires and Cables packaging (4)
Wires and Cables packaging (5)
Wires and Cables packaging (5)
Wires and Cables packaging (6)
Wires and Cables packaging (6)
Wires and Cables packaging (7)
Wires and Cables packaging (7)
Wires and Cables packaging (8)
Wires and Cables packaging (8)

Related Products

FAQ From Customers

What are the advantages of power cables and overhead lines?
(1) Reliable operation, because it is installed in a hidden place such as underground, it is less damaged by external forces, has less chance of failure, and the power supply is safe, and it will not cause harm to people;
(2) The maintenance workload is small and frequent inspections are not required;
(3) No need to erect towers;
(4) Help improve power factor.
Which aspects should be considered when choosing the cross section of a power cable?
(1) The long-term allowable working current of the cable;
(2) Thermal stability once short circuited;
(3) The voltage drop on the line cannot exceed the allowable working range.
What are the measures for cable fire prevention?
(1) Use flame-retardant cables;
(2) Use fireproof cable tray;
(3) Use fireproof paint;
(4) Fire partition walls and fire baffles are installed at cable tunnels, mezzanine exits, etc.;
(5) Overhead cables should avoid oil pipelines and explosion-proof doors, otherwise local pipes or heat insulation and fire prevention measures should be taken.
What should be paid attention to during the transportation and handling of cables?
(1) During transportation, loading and unloading, cables and cable reels should not be damaged. It is strictly forbidden to push the cable reels directly from the vehicle. Generally, cables should not be transported and stored flat.
(2) Before transporting or rolling the cable reel, ensure that the cable reel is firm, the cable is wound tightly, the oil pipe between the oil-filled cable and the pressure oil tank should be fixed without damage, the pressure oil tank should be firm, and the pressure indication should meet the requirements.
What inspections should be carried out for the acceptance of cable lines?
(1) The cable specifications should meet the regulations, the arrangement should be neat, no damage, and the signs should be complete, correct and clear;
(2) The fixed bending radius of the cable, the related distance and the wiring of the metal sheath of the single-core power cable should meet the requirements;
(3) The cable terminal and the middle head should not leak oil, and the installation should be firm. The oil pressure of the oil-filled cable and the meter setting should meet the requirements;
(4) Good grounding;
(5) The color of the cable terminal is correct, and the metal parts such as the bracket are completely painted;
(6) There should be no debris in the cable trench, tunnel, and bridge, and the cover should be complete.

Welcome your inquiry

Honesty, Integrity, Frugality, Activeness and Passion