x
1/0 Stranded Aluminum Conductor 35KV URD Cable
1/0 Stranded Aluminum Conductor 35KV URD Cable
1/0 Stranded Aluminum Conductor 35KV URD Cable
1/0 Stranded Aluminum Conductor 35KV URD Cable

1/0 Stranded Aluminum Conductor 35KV URD Cable

The 1/0 Stranded Aluminum Conductor 35kV URD Cable is a high-reliability medium-voltage underground distribution cable designed for primary power delivery. It features a 1/0 AWG stranded AA8000 aluminum alloy conductor, extruded semi-conducting shields, tree-retardant TR-XLPE insulation, copper concentric neutral wires, and a tough sunlight-resistant LLDPE jacket. This construction provides excellent electrical performance, superior moisture and treeing resistance, and strong mechanical protection suitable for direct burial or duct installations. The cable offers a good balance between ampacity and cost-effectiveness for medium voltage underground systems. Manufactured to ICEA S-94-649 and AEIC CS8 standards, the 1/0 Stranded Aluminum Conductor 35kV URD Cable undergoes rigorous quality testing from raw materials to finished product, ensuring long-term reliability and safety in demanding underground environments.
Voltage Rating 35 kV (100% or 133% insulation level)
Standards ICEA S-94-649, AEIC CS8
Partial Discharge ≤5 pC at 200 V/mil
Operating Tempe 90°C continuous, 130°C emergency, 250°C short-circuit
Jacket Black LLDPE (sunlight resistant)
Construction
Technical Specifications
Quality Control
Application

Construction

1/0 Stranded Aluminum Conductor 35KV URD Cable Construction
1/0 Stranded Aluminum Conductor 35KV URD Cable

Key Product Features

1/0 AWG AA8000 aluminum alloy conductor
Tree-retardant TR-XLPE insulation for enhanced longevity
Copper concentric neutral for effective shielding and grounding
Robust LLDPE jacket for mechanical and sunlight protection
Excellent moisture and corrosion resistance

Conductors

1/0 AWG Stranded AA8000 Aluminum Alloy

Concentric Neutral

Bare copper wires

Insulation

TR-XLPE (260 mils or 345 mils typical)

Configuration

Single conductor with concentric neutral

Insulation Shield

Semi-conducting XLPE

Technical Specifications

1/0 Stranded Aluminum Conductor 35KV URD Cable
1/0 Stranded Aluminum Conductor 35KV URD Cable

 

Item

Conductor Size

Neutral Size

Insulation Thickness

Jacket Thickness

Overall Diameter

(approx.)

Weight

(lbs/1000ft)

Ampacity*

(Direct Burial)

Ampacity*

(In Duct)

1

1/0 AWG

1/3 Neutral

260 mils (100% level)

50 mils

1.35 inches

680

285 Amps

225 Amps

2

1/0 AWG

1/3 Neutral

345 mils (133% level)

50 mils

1.52 inches

760

280 Amps

220 Amps

3

1/0 AWG

Full Neutral

260 mils (100% level)

50 mils

1.42 inches

780

285 Amps

225 Amps

4

1/0 AWG

Full Neutral

345 mils (133% level)

50 mils

1.60 inches

860

280 Amps

220 Amps

Notes:

  • Conductor Material: AA8000 Series Aluminum Alloy (Stranded)
  • Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE) or EPR
  • Neutral: Bare Copper Wires (1/3 or Full Neutral)
  • Jacket: Sunlight Resistant Black LLDPE
  • Voltage Rating: 35 kV
  • Standards: ICEA S-94-649, AEIC CS8, ASTM B800
  • Ampacity*: Based on 90°C conductor temperature, 20°C earth ambient, 100% load factor (values are approximate, please refer to local utility tables or NEC for exact engineering)

Quality Control

1/0 Stranded Aluminum Conductor 35KV URD Cable
Raw Material Test

Raw Material Test

Raw Material Test is the critical first step in manufacturing the 1/0 Stranded Aluminum Conductor 35kV URD Cable. Incoming AA8000 aluminum alloy rods undergo detailed chemical composition analysis to confirm precise alloy elements and purity levels. Mechanical testing verifies tensile strength, elongation, and hardness meet ASTM B800 requirements. TR-XLPE insulation compounds and semi-conducting materials are rigorously tested for thermal stability, dielectric strength, moisture resistance, and tree-retardant properties. Jacket materials are evaluated for UV stability and mechanical performance. Surface quality inspection and dimensional measurements detect any defects or inconsistencies. Only raw materials that fully pass every stringent criterion are approved for wire drawing, stranding, and extrusion in the production of the 1/0 Stranded Aluminum Conductor 35kV URD Cable. This thorough incoming inspection guarantees consistent high electrical performance, mechanical strength, and long-term reliability in medium-voltage underground applications.

 

Process inspection

Process inspection

Process Inspection during manufacturing of the 1/0 Stranded Aluminum Conductor 35kV URD Cable maintains precise control at every stage. After conductor stranding, continuous monitoring verifies dimensional tolerances and surface quality. Triple extrusion of conductor shield, insulation, and insulation shield is carefully controlled for uniform thickness and clean interfaces. The concentric copper neutral application uses real-time tension control and lay length verification to ensure even helical winding. LLDPE jacket extrusion is monitored for proper thickness and adhesion. Online diameter measurement systems and frequent visual checks prevent defects such as voids or uneven layers. Key process parameters, including temperature and speed, are strictly logged. Mid-process sampling includes partial discharge and electrical tests. Any deviation triggers immediate corrective action. These rigorous in-process controls safeguard the structural integrity and electrical properties of the 1/0 Stranded Aluminum Conductor 35kV URD Cable, delivering a high-quality medium-voltage cable ready for underground service.

 

Finished Product

Finished Product

Finished Product testing ensures every reel of 1/0 Stranded Aluminum Conductor 35kV URD Cable meets the highest quality standards. Comprehensive dimensional verification confirms overall diameter, insulation thickness, and concentric neutral coverage. DC resistance, high-voltage AC, and partial discharge tests validate electrical performance per ICEA and AEIC requirements. Mechanical tests measure tensile strength and elongation. Full visual and tactile inspections check for surface defects or jacket imperfections. All examinations follow ICEA S-94-649 and AEIC CS8 standards with detailed records for full traceability. Packaging and marking accuracy are also verified. Only the 1/0 Stranded Aluminum Conductor 35kV URD Cable that successfully passes 100% of these final inspections receives approval for shipment. This rigorous final quality gate assures customers of outstanding dielectric strength, moisture resistance, and reliable performance in medium-voltage underground distribution applications.

Application

The 1/0 Stranded Aluminum Conductor 35kV URD Cable is ideal for underground primary distribution networks, URD systems, feeder circuits, substation connections, and municipal power grids requiring reliable medium-voltage underground cable with good ampacity and durability.

Technical Advantages

● 30+ years of manufacturing experience
● ISO and UL certified production
● Customized cable and transformer solutions

Product Packaging

Wires and Cables packaging (1)
Wires and Cables packaging (1)
Wires and Cables packaging (2)
Wires and Cables packaging (2)
Wires and Cables packaging (3)
Wires and Cables packaging (3)
Wires and Cables packaging (4)
Wires and Cables packaging (4)
Wires and Cables packaging (5)
Wires and Cables packaging (5)
Wires and Cables packaging (6)
Wires and Cables packaging (6)
Wires and Cables packaging (7)
Wires and Cables packaging (7)
Wires and Cables packaging (8)
Wires and Cables packaging (8)

Related Products

FAQ From Customers

What are the advantages of power cables and overhead lines?
(1) Reliable operation, because it is installed in a hidden place such as underground, it is less damaged by external forces, has less chance of failure, and the power supply is safe, and it will not cause harm to people;
(2) The maintenance workload is small and frequent inspections are not required;
(3) No need to erect towers;
(4) Help improve power factor.
Which aspects should be considered when choosing the cross section of a power cable?
(1) The long-term allowable working current of the cable;
(2) Thermal stability once short circuited;
(3) The voltage drop on the line cannot exceed the allowable working range.
What are the measures for cable fire prevention?
(1) Use flame-retardant cables;
(2) Use fireproof cable tray;
(3) Use fireproof paint;
(4) Fire partition walls and fire baffles are installed at cable tunnels, mezzanine exits, etc.;
(5) Overhead cables should avoid oil pipelines and explosion-proof doors, otherwise local pipes or heat insulation and fire prevention measures should be taken.
What should be paid attention to during the transportation and handling of cables?
(1) During transportation, loading and unloading, cables and cable reels should not be damaged. It is strictly forbidden to push the cable reels directly from the vehicle. Generally, cables should not be transported and stored flat.
(2) Before transporting or rolling the cable reel, ensure that the cable reel is firm, the cable is wound tightly, the oil pipe between the oil-filled cable and the pressure oil tank should be fixed without damage, the pressure oil tank should be firm, and the pressure indication should meet the requirements.
What inspections should be carried out for the acceptance of cable lines?
(1) The cable specifications should meet the regulations, the arrangement should be neat, no damage, and the signs should be complete, correct and clear;
(2) The fixed bending radius of the cable, the related distance and the wiring of the metal sheath of the single-core power cable should meet the requirements;
(3) The cable terminal and the middle head should not leak oil, and the installation should be firm. The oil pressure of the oil-filled cable and the meter setting should meet the requirements;
(4) Good grounding;
(5) The color of the cable terminal is correct, and the metal parts such as the bracket are completely painted;
(6) There should be no debris in the cable trench, tunnel, and bridge, and the cover should be complete.

Welcome your inquiry

Honesty, Integrity, Frugality, Activeness and Passion