(N)TSCGEWOU 3.6/6kV, 6/10kV, 8.7/15kV and 12/20kV ZH Cable
(N)TSCGEWOU 3.6/6kV, 6/10kV, 8.7/15kV and 12/20kV ZH Cable

(N)TSCGEWOU 3.6/6kV, 6/10kV, 8.7/15kV and 12/20kV ZH Cable

The (N)TSCGEWOU 3.6/6kV, 6/10kV, 8.7/15kV, and 12/20kV ZH Cable is a halogen-free flexible medium voltage power cable designed in accordance with VDE 0250 standards for heavy-duty applications. It features Class 5 tinned copper conductors, EPR insulation, semi-conductive layers, and a copper braided earth conductor, with an inner and outer halogen-free polyurethane sheath that delivers excellent flame retardancy, low smoke emission, and high mechanical durability. Ideal for draglines, shovels, dredges, and drills in opencast mining or other extreme environments, this cable is suitable for both indoor and outdoor use where fire safety and robust performance are critical.
Voltage Rating Uo/U 3.6/6kV | 6/10kV | 8.7/15kV | 12/20kV
Test Voltage 3.6/6kV: 11kV
6/10kV: 17kV
8.7/15kV: 24kV
12/20kV: 29kV
Temperature Rating Fixed: -50°C to +80°C
Flexed: -25°C to +80°C
Minimum Bending Radius Fixed: 6 x overall diameter
Flexed: 10 x overall diameter
Maximum Torsional Stress ±25°/m
Construction
Technical Specifications
Quality Control
Application

Construction

(N)TSCGEWOU 3.6/6kV, 6/10kV, 8.7/15kV and 12/20kV ZH Cable Constrution
(N)TSCGEWOU 3.6/6kV, 6/10kV, 8.7/15kV and 12/20kV ZH Cable

Phase Conductor

lass 5 tinned copper

Insulation

Rubber compound

Earth Conductor

Class 5 tinned copper conductor

Central Filler

Semi-conductive compound on a polyester textile support

Inner Sheath

Halogen-free polyurethane

Anti-Torsion Braid

Polyester braid between the inner and outer sheath

Outer Sheath

Halogen-free polyurethane

Sheath Colour

Yellow

Manufacturer Standard

VDE 0250 Part 813, HD 22.16 , VDE 0295, EN 60228

Flame Retardant

IEC/EN 60332-1-2

Halogen Free

IEC/EN 60754-1/2

Semi-Conductive Layers

Semi-conductive tape over the conductor and inner and outer
Semi-conductive rubber layer on the insulation

Application

(N)TSCGEWOU 3.6/6kV, 6/10kV, 8.7/15kV and 12/20kV ZH Cable is used for supplying power to heavy mobile equipment such as draglines, shovels, dredges, and drills operating under extreme mechanical stress in opencast mines. Its halogen-free polyurethane sheath makes it suitable for both indoor and outdoor environments requiring high flame safety and durability.

Technical Specifications

(N)TSCGEWOU 3.6/6kV, 6/10kV, 8.7/15kV and 12/20kV ZH Cable
(N)TSCGEWOU 3.6/6kV ZH Cable
(N)TSCGEWOU 6/10kV ZH Cable
(N)TSCGEWOU 8.7/15kV ZH Cable
(N)TSCGEWOU 12/20kV ZH Cable

No. Of Cores
(PHASE+EARH)

Nominal Cross Sectional Area
mm²

CONDUCTOR

DIAMETER

MINIMUM OVERALL

DIAMETER

MAXIMUM OVERALL

DIAMETER

MAXIMUM

TENSILE LOAD

NOMINAL

WEIGHT

Phase

Conductor

Earth

Conductor

mm mm mm N kg/km
3+3 25 25/3 6.8 37.4 38.6 1500 2280
3+3 35 25/3 7.8 39 40.2 2100 2630
3+3 50 25/3 9.4 42.0 43.7 3000 3230
3+3 70 35/3 11.2 45.8 47.5 4200 4160
3+3 95 50/3 12.7 50 51.8 5700 5080
3+3 120 70/3 14.4 53.8 55.6 7200 6280
3+3 150 70/3 16.3 59.3 61.1 9000 7570
3+3 185 95/3 17.6 61.1 63.4 11100 8740

No. Of Cores
(PHASE+EARH)

Nominal Cross Sectional Area
mm²

CONDUCTOR

DIAMETER

MINIMUM OVERALL

DIAMETER

MAXIMUM OVERALL

DIAMETER

MAXIMUM

TENSILE LOAD

NOMINAL

WEIGHT

Phase

Conductor

Earth

Conductor

mm mm mm N kg/km
3+3 25 25/3 6.8 37.4 39.2 1500 2320
3+3 35 25/3 7.8 39 40.8 2100 2670
3+3 50 25/3 9.4 42.0 44.3 3000 3270
3+3 70 35/3 11.2 45.8 48.1 4200 4200
3+3 95 50/3 12.7 50 52.4 5700 5120
3+3 120 70/3 14.4 53.8 56.3 7200 6320
3+3 150 70/3 16.3 59.3 61.8 9000 7610
3+3 185 95/3 17.6 61.1 64.1 11100 8780

No. Of Cores
(PHASE+EARH)

Nominal Cross Sectional Area
mm²

CONDUCTOR

DIAMETER

MINIMUM OVERALL

DIAMETER

MAXIMUM OVERALL

DIAMETER

MAXIMUM

TENSILE LOAD

NOMINAL

WEIGHT

Phase

Conductor

Earth

Conductor

mm mm mm N kg/km
3+3 25 25/3 6.8 40.7 42.4 1500 2580
3+3 35 25/3 7.8 42.2 43.9 2100 2930
3+3 50 25/3 9.4 45.4 47.1 3000 3560
3+3 70 35/3 11.2 49.2 51 4200 4510
3+3 95 50/3 12.7 52.6 54.4 5700 5360
3+3 120 70/3 14.4 57.2 59 7200 6690
3+3 150 70/3 16.3 61.7 64 9000 7910
3+3 185 95/3 17.6 63.8 66.1 11100 9110

No. Of Cores
(PHASE+EARH)

Nominal Cross Sectional Area
mm²

CONDUCTOR

DIAMETER

MINIMUM OVERALL

DIAMETER

MAXIMUM OVERALL

DIAMETER

MAXIMUM

TENSILE LOAD

NOMINAL

WEIGHT

Phase

Conductor

Earth

Conductor

mm mm mm N kg/km
3+3 25 25/3 6.8 43.3 45 1500 2810
3+3 35 25/3 7.8 44.8 46.5 2100 3160
3+3 50 25/3 9.4 47.9 49.6 3000 3810
3+3 70 35/3 11.2 51.7 53.5 4200 4780
3+3 95 50/3 12.7 55.1 56.9 5700 5660
3+3 120 70/3 14.4 59.6 61.9 7200 7020
3+3 150 70/3 16.3 64.2 66.5 9000 8250
3+3 185 95/3 17.6 66.3 68.6 11100 9460

Quality Control

(N)TSCGEWOU 3.6/6kV, 6/10kV, 8.7/15kV and 12/20kV ZH Cable
(N)TSCGEWOU 3.6/6kV, 6/10kV, 8.7/15kV and 12/20kV ZH Cable Raw Material Test

Raw Material Test

NPC has always chosen raw material suppliers who have a good reputation, possess stable supply capabilities and have passed international quality system certifications (such as ISO 9001). And establish a long-term cooperative relationship with it, forming a stable and reliable raw material supply chain.
We will ensure that all raw materials are subject to strict inspection procedures upon entry to the factory, and can only be stored in the warehouse after they have been confirmed to meet the standards.

(N)TSCGEWOU 3.6/6kV, 6/10kV, 8.7/15kV and 12/20kV ZH Cable Process inspection

Process inspection

NPC has strict quality control procedures for each process in the cable production process.
Process documents: Develop detailed process flow and operation instructions to clarify the operating specifications and quality standards of each process.
Equipment calibration: Regularly calibrate key equipment such as wire drawing machines, stranding machines, extruders, and diameter gauges to ensure that the accuracy meets the requirements.
First piece confirmation: Before each batch of production, the first piece is trial-produced to confirm that the process parameters, product dimensions, electrical performance, etc. meet the standards before mass production can be carried out.

(N)TSCGEWOU 3.6/6kV, 6/10kV, 8.7/15kV and 12/20kV ZH Cable Finished Product

Finished Product

Inspectors conduct ex-factory inspections on cables according to relevant standards and corresponding product inspection specifications to ensure that each ex-factory product complies with the process regulations.

Application

The ZH Cable is used for supplying power to heavy mobile equipment such as draglines, shovels, dredges, and drills operating under extreme mechanical stress in opencast mines. Its halogen-free polyurethane sheath makes it suitable for both indoor and outdoor environments requiring high flame safety and durability.

Technical Advantages

● 30+ years of manufacturing experience
● ISO and UL certified production
● Customized cable and transformer solutions

Product Packaging

Wires and Cables packaging (1)
Wires and Cables packaging (1)
Wires and Cables packaging (2)
Wires and Cables packaging (2)
Wires and Cables packaging (3)
Wires and Cables packaging (3)
Wires and Cables packaging (4)
Wires and Cables packaging (4)
Wires and Cables packaging (5)
Wires and Cables packaging (5)
Wires and Cables packaging (6)
Wires and Cables packaging (6)
Wires and Cables packaging (7)
Wires and Cables packaging (7)
Wires and Cables packaging (8)
Wires and Cables packaging (8)

Related Products

FAQ From Customers

What are the advantages of power cables and overhead lines?
(1) Reliable operation, because it is installed in a hidden place such as underground, it is less damaged by external forces, has less chance of failure, and the power supply is safe, and it will not cause harm to people;
(2) The maintenance workload is small and frequent inspections are not required;
(3) No need to erect towers;
(4) Help improve power factor.
Which aspects should be considered when choosing the cross section of a power cable?
(1) The long-term allowable working current of the cable;
(2) Thermal stability once short circuited;
(3) The voltage drop on the line cannot exceed the allowable working range.
What are the measures for cable fire prevention?
(1) Use flame-retardant cables;
(2) Use fireproof cable tray;
(3) Use fireproof paint;
(4) Fire partition walls and fire baffles are installed at cable tunnels, mezzanine exits, etc.;
(5) Overhead cables should avoid oil pipelines and explosion-proof doors, otherwise local pipes or heat insulation and fire prevention measures should be taken.
What should be paid attention to during the transportation and handling of cables?
(1) During transportation, loading and unloading, cables and cable reels should not be damaged. It is strictly forbidden to push the cable reels directly from the vehicle. Generally, cables should not be transported and stored flat.
(2) Before transporting or rolling the cable reel, ensure that the cable reel is firm, the cable is wound tightly, the oil pipe between the oil-filled cable and the pressure oil tank should be fixed without damage, the pressure oil tank should be firm, and the pressure indication should meet the requirements.
What inspections should be carried out for the acceptance of cable lines?
(1) The cable specifications should meet the regulations, the arrangement should be neat, no damage, and the signs should be complete, correct and clear;
(2) The fixed bending radius of the cable, the related distance and the wiring of the metal sheath of the single-core power cable should meet the requirements;
(3) The cable terminal and the middle head should not leak oil, and the installation should be firm. The oil pressure of the oil-filled cable and the meter setting should meet the requirements;
(4) Good grounding;
(5) The color of the cable terminal is correct, and the metal parts such as the bracket are completely painted;
(6) There should be no debris in the cable trench, tunnel, and bridge, and the cover should be complete.