A2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable
A2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable

A2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable

The A2XS(FL)2Y MDPE High Voltage Power Cable is a single-core aluminum conductor cable with XLPE insulation and an MDPE sheath, rated 36/60 (72.5) kV. Designed for high-voltage power transmission, it meets IEC 60840 standards, offering excellent electrical performance, mechanical protection, and water resistance. Its construction features an aluminum conductor, semi-conductive conductor screen, XLPE insulation, semi-conductive insulation screen, semi-conductive water swelling tape, copper wire metallic screen, longitudinal aluminum tape with PE copolymer coating, and an MDPE sheath. Water-blocking tape prevents water propagation, ensuring reliable operation in power stations, industrial plants, and distribution networks. Suitable for underground, underwater, indoor, outdoor, and duct installations, this cable is ideal for distribution networks, connections to generation units, and industrial processes.
Voltage Rating(Uo/U)(Um) 36/60 kV (72.5kV)
Construction
Technical Specifications
Quality Control
Application

Construction

A2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable Constrution
A2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable

Conductor

Aluminium conductor (optional watertightness – WTC)

Conductor Screen

Semi-conductive screen extruded on the phase conductor

Insulation

XLPE (Cross-Linked Polyethylene)

Insulation Screen

Semi-conductive screen extruded on insulation

Wrapping

Semi-conductive water swelling tape

Metallic Screen

Copper wires and equalising tape

Sheath

MDPE (Medium Density Polyethylene)Optional —semi-conductive layer

Sheath Colour

Black

Manufacturer Standard

IEC 60840

Tape

Longitudinally applied aluminium tape coated with PE copolymer

Application

A2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable is suitable for distribution networks, connections to generation units, and industrial plants, with installation options including underground, underwater, outdoor, indoor, and cable ducts.

Technical Specifications

A2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable
A2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable
No. Of Cores

NOMINAL CROSS

SECTIONAL AREA

mm²

INSULATION
mm
METALLIC SCREEN

NOMINAL

WEIGHT

kg/km

MAXIMUM PULLING

FORCE

kN

Nominal Thickness

Nominal Diameter

Over

Nominal Cross

Section

mm²

Nominal Diameter

Over

mm

1 120RM 10.0 33.7 35 37.5 1920 4.2
1 150RM 10.0 35.3 35 39.1 2070 5.3
1 185RM 10.0 37.0 35 40.8 2240 6.5
1 240RM 10.0 39.1 35 42.9 2480 8.4
1 300RM 10.0 41.2 35 45.0 2750 10.5
1 400RM 10.0 44.5 35 48.7 3190 14.0
1 500RM 10.0 47.3 35 51.5 3630 17.5
1 630RM 10.0 51.1 35 55.3 4220 22.1
1 800RM 10.0 54.8 35 59.0 4860 28.0
1 1000RM 10.0 60.2 35 64.8 5800 35.0
1 1200RM 10.0 64.7 50 69.3 6580 42.0
1 1200RMS 10.0 67.2 50 71.8 7070 42.0
1 1400RMS 10.0 69.3 50 73.9 7750 49.0
1 1600RMS 10.0 72.7 50 77.3 8520 56.0
1 1800RMS 10.0 76.9 50 81.5 9450 63.0
1 2000RMS 10.0 78.7 50 83.3 10020 70.0
1 2500RMS 10.0 84.2 50 89.2 11530 87.5
1 3000RMS 10.0 92.2 50 97.2 13990 100.0

Quality Control

A2XS(FL)2Y MDPE High Voltage 36/60 (72.5)kV Power Cable
Raw Material Test

Raw Material Test

Raw Material Test for A2XS(FL)2Y MDPE 36/60 (72.5) kV Power Cable prioritizes HV-grade quality and water-blocking. Steps include: Certification Check: Aluminium conductors and XLPE verified to IEC 60228/IEC 60840 standards. Conductor Testing: Tensile, elongation, conductivity analysis. XLPE Evaluation: Tensile, elongation, dielectric strength, water tree resistance, hot set test. Semi-Conductive & Shielding Checks: Resistivity, adhesion, Cu wire/Al foil coverage/conductivity. Water-Blocking Testing: Swellable tapes/powders for longitudinal sealing efficiency. MDPE Sheath Testing: Tensile, ESCR, UV stability, mechanical properties. Batch Rejection: Non-compliant quarantined. Approved materials ensure the A2XS(FL)2Y MDPE 36/60 (72.5) kV Power Cable's HV performance and water protection.

Process inspection

Process inspection

Process Inspection for A2XS(FL)2Y MDPE 36/60 (72.5) kV Power Cable enforces HV precision. The procedure features: Stranding Control: Uniform conductor stranding. Triple Extrusion: Conductor screen, XLPE, insulation screen monitored. Water-Blocking: Longitudinal tapes/powders inserted. Screening: Cu wire + Al foil applied precisely. Sheath Extrusion: MDPE sheath with thickness/adhesion checks. Correction: Immediate fixes. This guarantees the A2XS(FL)2Y MDPE 36/60 (72.5) kV Power Cable excels in HV transmission with water-blocking.

Finished Product

Finished Product

Finished Product Test validates the A2XS(FL)2Y MDPE 36/60 (72.5) kV Power Cable for deployment. Steps include: Inspection: Visual/dimensional/marking verification. Electrical: Resistance, insulation, withstand (95kV/1h), partial discharge. Water-Blocking: Longitudinal penetration test. Mechanical: Bending, tensile, crush resistance. Performance: Thermal aging, water penetration, UV/ESCR checks. Release: Only passing A2XS(FL)2Y MDPE 36/60 (72.5) kV Power Cable approved for reliable HV use.

Application

The A2XS(FL)2Y MDPE 36/60 (72.5) kV Power Cable is suited for 36/60 kV underground transmission lines, direct-buried distribution networks, industrial HV feeders, substation interconnections, renewable energy connections, and wet/aggressive soil HV installations requiring XLPE-insulated, longitudinally water-blocked cable with high electrical and mechanical performance.

Technical Advantages

● 30+ years of manufacturing experience
● ISO and UL certified production
● Customized cable and transformer solutions

Product Packaging

Wires and Cables packaging (1)
Wires and Cables packaging (1)
Wires and Cables packaging (2)
Wires and Cables packaging (2)
Wires and Cables packaging (3)
Wires and Cables packaging (3)
Wires and Cables packaging (4)
Wires and Cables packaging (4)
Wires and Cables packaging (5)
Wires and Cables packaging (5)
Wires and Cables packaging (6)
Wires and Cables packaging (6)
Wires and Cables packaging (7)
Wires and Cables packaging (7)
Wires and Cables packaging (8)
Wires and Cables packaging (8)

Related Products

FAQ From Customers

What are the advantages of power cables and overhead lines?
(1) Reliable operation, because it is installed in a hidden place such as underground, it is less damaged by external forces, has less chance of failure, and the power supply is safe, and it will not cause harm to people;
(2) The maintenance workload is small and frequent inspections are not required;
(3) No need to erect towers;
(4) Help improve power factor.
Which aspects should be considered when choosing the cross section of a power cable?
(1) The long-term allowable working current of the cable;
(2) Thermal stability once short circuited;
(3) The voltage drop on the line cannot exceed the allowable working range.
What are the measures for cable fire prevention?
(1) Use flame-retardant cables;
(2) Use fireproof cable tray;
(3) Use fireproof paint;
(4) Fire partition walls and fire baffles are installed at cable tunnels, mezzanine exits, etc.;
(5) Overhead cables should avoid oil pipelines and explosion-proof doors, otherwise local pipes or heat insulation and fire prevention measures should be taken.
What should be paid attention to during the transportation and handling of cables?
(1) During transportation, loading and unloading, cables and cable reels should not be damaged. It is strictly forbidden to push the cable reels directly from the vehicle. Generally, cables should not be transported and stored flat.
(2) Before transporting or rolling the cable reel, ensure that the cable reel is firm, the cable is wound tightly, the oil pipe between the oil-filled cable and the pressure oil tank should be fixed without damage, the pressure oil tank should be firm, and the pressure indication should meet the requirements.
What inspections should be carried out for the acceptance of cable lines?
(1) The cable specifications should meet the regulations, the arrangement should be neat, no damage, and the signs should be complete, correct and clear;
(2) The fixed bending radius of the cable, the related distance and the wiring of the metal sheath of the single-core power cable should meet the requirements;
(3) The cable terminal and the middle head should not leak oil, and the installation should be firm. The oil pressure of the oil-filled cable and the meter setting should meet the requirements;
(4) Good grounding;
(5) The color of the cable terminal is correct, and the metal parts such as the bracket are completely painted;
(6) There should be no debris in the cable trench, tunnel, and bridge, and the cover should be complete.