x
750kVA 3-Phase Oil-Immersed Outdoor Substation Transformer 1
750kVA 3-Phase Oil-Immersed Outdoor Substation Transformer 2
750kVA 3-Phase Oil-Immersed Outdoor Substation Transformer 3
750kVA 3-Phase Oil-Immersed Outdoor Substation Transformer 4
750kVA 3-Phase Oil-Immersed Outdoor Substation Transformer 1
750kVA 3-Phase Oil-Immersed Outdoor Substation Transformer 2
750kVA 3-Phase Oil-Immersed Outdoor Substation Transformer 3
750kVA 3-Phase Oil-Immersed Outdoor Substation Transformer 4

750kVA 3-Phase Oil-Immersed Outdoor Substation Transformer

A 750kVA 3-phase oil-immersed outdoor substation transformer is designed for stable and efficient power distribution in industrial, commercial, and utility applications. Built with high-quality insulation and premium transformer oil, it provides excellent cooling performance and long-term reliability. The transformer ensures accurate current measurement and voltage conversion, making it ideal for outdoor substations operating under demanding conditions.
Primary Voltage Ratings 34.5-19.92/13.8-7.957/13.2-7.62/12.47-7.2, 33 or others
Secondary Voltage Ratings 480/277V, 400/230V, 380/220V or customized
H.V. Tap Range ± 2×2.5% HV taps or others
Type Oil immersed transformer
BIL 30/95kV
Standards IEEE, ANSI, NEMA, IEC, CE
Application Power Substations, Industrial Power Supply
Power Rating 750kVA
Certificate UL, CESI, IEEE
Cooling Method ONAN, ONAN/ONAF, KNAN, KNAN/KNAF
Oil Mineral Oil or FR3
Opeartion Step Down & Step Up
Technical Specifications
Customization Optional
Packing and Shipping
Manufacturer Test
Routine Testing
Application

Technical Specifications

750kVA 3-Phase Oil-Immersed Outdoor Substation Transformer
Technical Specifications
Accessories
Rated Power 750 kVA
Rating Primary Voltage 2.4 - 34.5kV
Secondary Voltage 480/277V
400/230V
380/220V
Customized
Frequency 50/60Hz
Vector Group Dyn11, Yyn0, Dyn5
Winding Material Aluminum/Copper
Efficiency As IEEE, Doe 2016, CAS Std or Customized
Impedance Voltage Nominal 2% or Customized 1.1 - 5.75% 
Altitude ≤1,000m or Customized
Color ANSI 70 Light gray/Munsell 7GY3.29/1.5 or customized, etc
Tank material Mild Steel, 304 Stainless Steel
Insulating Oil Weight 900 kg
Total Weight 3100 kg
Outline Dimensions(L×W×H)in. 1950 × 1060 × 1900(mm)
HV Bushing
LV Bushing
Tap changer
Oil level gauge
Oil temperature indicator
Pressure relief device
Pressure vacuum gauge
Lifting hook for complete transformer
Name plate
Radiators
Oil upper filtering valve
Oil drain valve with 3/8" sampler

Customization Optional

750kVA 3-Phase Oil-Immersed Outdoor Substation Transformer
Our 750kVA 3-phase oil-immersed outdoor substation transformer can be fully customized to meet different installation and operational requirements. Voltage levels, current ratios, and winding configurations can be tailored to match local grid standards or specific industrial applications. Customers may choose between various cooling methods, insulation classes, and tap changer options—manual or on-load—to achieve precise voltage regulation. We also offer customization for protection devices, monitoring systems, and surge arresters to enhance safety and real-time performance monitoring.
Additionally, the transformer’s enclosure design, protection rating, and oil type can be adjusted based on the environmental conditions of the installation site. Options include anti-corrosion coatings for coastal regions, reinforced bushings for high-altitude areas, and eco-friendly or high-fire-resistance transformer oils. Custom testing, certifications, and branding are available to comply with regional standards or project requirements. These flexible customization solutions ensure that every 750kVA oil-immersed substation transformer delivers optimal, long-lasting performance.

Packing and Shipping

750kVA 3-Phase Oil-Immersed Outdoor Substation Transformer
To ensure the 750kVA 3-Phase Oil-Immersed Outdoor Substation Transformer arrives at its destination in perfect condition, we strictly follow international heavy electrical equipment transportation standards with professional packing and shipping procedures.
After completing all factory routine, type, and special tests, the transformer is vacuum-treated and filled with high-purity nitrogen to maintain positive internal pressure throughout transit. This effectively prevents moisture ingress and oil oxidation during long-distance transportation. High-voltage and low-voltage bushings, oil level gauges, thermometers, sudden pressure relays, and other fragile accessories are carefully removed and packed in custom-made wooden crates lined with high-density anti-shock foam and desiccant for maximum protection.
The transformer body is securely mounted on a reinforced steel saddle skid designed for heavy load distribution. It is then fully enclosed in a robust wooden crate constructed from 12mm-thick marine-grade plywood and 50×50mm steel framing. The entire crate is double-wrapped with waterproof and moisture-proof film. All timber materials are IPPC-certified and fumigated with clear markings. The exterior is clearly labeled in English and Chinese with “750kVA 3-Phase Oil-Immersed Outdoor Substation Transformer,” lifting points, center-of-gravity indicators, handling instructions, and moisture warnings. Four high-precision shock recorders are attached to monitor impact and vibration throughout the journey.
For shipping, we offer flexible solutions including road transport via hydraulic modular trailers or low-bed trailers (total height controlled under 5 meters), sea freight in 40ft flat-rack containers or break-bulk under-deck stowage secured with DNV/GL-approved lashing using Φ18mm wire ropes and turnbuckles, and air freight options for urgent deliveries. Full documentation—including packing list, certificate of origin, fumigation certificate, nitrogen pressure report, shock recorder baseline data, and detailed installation manual—is provided with every shipment. With these rigorous measures, the 750kVA 3-Phase Oil-Immersed Outdoor Substation Transformer is guaranteed damage-free delivery worldwide, ready for immediate high-voltage power distribution installation.
Oil Immersed Transformer package
Oil Immersed Transformer package mini
32
32 years of industry experience

Manufacturer Test

750kVA 3-Phase Oil-Immersed Outdoor Substation Transformer
Oil Immersed Transformer Progress Test

Progress Test

The 750kVA 3-Phase Oil-Immersed Outdoor Substation Transformer undergoes rigorous Progress Tests at critical manufacturing stages to guarantee superior quality and reliability. Following core-coil assembly, tests include winding insulation resistance (PI ≥ 2.0), DC resistance measurement at all taps, core grounding current (<50 mA), and preliminary no-load loss verification. Before tanking, the voltage ratio at every tap position (deviation ≤ ±0.5%) and vector group (Dyn11) are precisely confirmed to ensure electrical performance meets design specifications.

After vapor-phase drying and vacuum oil-filling, final insulation resistance, dielectric dissipation factor (tanδ ≤ 0.004 at 20℃), and partial discharge (<5 pC at 1.5Um/√3) are measured under witness. The completely assembled transformer then passes a 24-hour oil leakage test and a 0.35 bar positive/negative pressure test for 24 hours. All Progress Test records are fully documented and submitted for client or third-party approval, ensuring each 750kVA 3-Phase Oil-Immersed Outdoor Substation Transformer fully complies with IEC 60076 and project requirements before proceeding to final testing and delivery.

Oil Immersed Transformer  Design Tests

Design Tests

All transformer will be test after finished the production, test items as below:
♦ Insulation Power Factor
♦ Ratio, Polarity, and Phase Relation
♦ Winding Resistance
♦ Impulse Tests
♦ On load Loss Test
♦ No Load Loss Test
♦ Leak Test
♦ DC Insulation Resistance Test
♦ Transformer Turns Ratio/TTR (All Tap Voltages)
♦ Impedance Voltage & Load Loss (Rated Voltage)
♦ Polarity, 1-Ph / Phase Relation, 3-Ph (Rated Voltage)
♦ Excitation & No-Load Loss (Rated Voltage)
♦ Applied Voltage
♦ Induced Voltage
♦ Lightning Impulse
♦ Insulation Resistance (Rated Voltage)
♦ Temperature Rise
♦ Dielectric Withstand (Hipot)

China NPC ELECTRIC

Transformer Factory Acceptance Test

The 750kVA 3-Phase Oil-Immersed Outdoor Substation Transformer undergoes comprehensive Factory Acceptance Tests in strict accordance with IEC 60076, GB/T 1094, and project technical specifications, witnessed by client or third-party inspectors.

Key tests include:

  1. Winding resistance measurement at all tap positions
  2. Voltage ratio and phase displacement verification at principal, ±2.5% and ±5% taps (deviation ≤ ±0.5%)
  3. Vector group and polarity confirmation (Dyn11)
  4. No-load loss and no-load current at 90%, 100%, and 110% rated voltage
  5. Load loss and short-circuit impedance at rated current and principal tap (tolerance per IEC)
  6. Applied voltage test (separate-source withstand)

All results are recorded in the official FAT protocol, signed by the client representative upon acceptance, ensuring the transformer is fully qualified for high-voltage power distribution service.

Routine Test - Temperature Rise

Purpose of Testing
The purpose of the temperature rise test is to detect the temperature change of the equipment under working conditions by applying the rated load current or higher load current to ensure that the insulation performance of the equipment will not be degraded or damaged due to overheating during operation.
Testing Equipment
Temperature rise tester (e.g. OMRON, FLIR, Extech, etc.)
Heating source
Temperature sensor
Voltage source
Temperature and humidity meter
Pre-Test Preparation
Disconnect the device from the power supply and ensure that the device is properly grounded and discharged. Ensure that the connection terminals and wiring are firm to avoid looseness affecting the test results. Test under suitable environmental conditions: relative humidity below 75%, no rain (recommended temperature: 20-30°C).
Test Progress
Connect the Test Instrument:
Connect the test instrument correctly to the electrical terminals and temperature measurement points of the device under test . Ensure that the test system is well grounded to ensure test safety.
Initial condition record:
Measure and record ambient temperature, humidity, and atmospheric pressure at the start of the test.
Measure and Record
Record the following parameters regularly: Temperature of each winding (by resistance method or temperature sensor); Core temperature; Oil temperature (for oil-immersed equipment); Current, voltage and power at the equipment end; Duration of load; Record changes in ambient temperature.
Temperature Correction
Correct the measured winding temperature rise (equipment temperature - ambient temperature) to the reference ambient temperature (usually 20°C or as required by the standard).
Repeat Testing (if necessary)
If the load is unstable or the measurement is abnormal during the test, reload and repeat the test process.
Evaluation Criteria (Reference)
The maximum temperature rise of the winding should not exceed the product standard or the manufacturer's specified value (for example: Class A insulation: ≤60°C temperature rise; Class B insulation: ≤80°C temperature rise; Class F insulation: ≤100°C temperature rise)
*These comprehensive tests ensure that each transformer meets performance standards and operates reliably under various conditions.
Oil Immersed Transformer Routine Test

Application

Industrial Parks and Manufacturing Plants, Commercial Complexes and Data Centers, Renewable Energy Projects, Urban and Rural Distribution Networks

Technical Advantages

● 30+ years of manufacturing experience
● ISO and UL certified production
● Customized cable and transformer solutions

Product Packaging

Transformers Packaging (1)
Transformers Packaging (1)
Transformers Packaging (2)
Transformers Packaging (2)
Transformers Packaging (3)
Transformers Packaging (3)
Transformers Packaging (4)
Transformers Packaging (4)
Transformers Packaging (5)
Transformers Packaging (5)
Transformers Packaging (6)
Transformers Packaging (6)
Transformers Packaging (7)
Transformers Packaging (7)
Transformers Packaging (8)
Transformers Packaging (8)

Related Products

FAQ From Customers

What is a Transformer?
A transformer is an electrical device used to change the voltage of alternating current (AC). It works on the principle of electromagnetic induction, converting high-voltage current into low-voltage current or low-voltage current into high-voltage current. Transformers are widely used in power transmission, distribution systems, and various electronic devices.
What are the main uses of a transformer?
The main use of a transformer is voltage conversion. Transformers are used in power transmission systems to help transfer electricity from power plants to consumers. In addition, transformers are also used in electronic devices such as chargers, televisions, power adapters, etc., to adjust the voltage to meet the requirements of different devices.
Do you have UL listed?
Yes, our transformer has UL listed. We have exported to America many pad mounted transformer,substation transformer and HV.

Welcome your inquiry

Honesty, Integrity, Frugality, Activeness and Passion