75kV 1250kVA Three Phase Oil Immersed Power Transformer Copper
- Primary Voltage Ratings 69kV 66kV 75kV or others
- Secondary Voltage Ratings 33/13.8/11 kV or customized
- H.V. Tap Range ±8×1.25% or others
- Type Oil-immersed power transformer
- BIL Up to 350kV
- Standards IEEE, ANSI, IEC, CSA
- Application wind/solar grid connection, petrochemical facilities, railway traction, urban high-voltage distribution
- Power Rating 1250kVA
- Certificate UL ,CESI ,ISO
- Cooling Method ONAN/ ONAF
- Opeartion Step Down & Step Up
Technical Specifications
| Rated Power | 1250kVA |
| Rating Primary Voltage | 69kV 66kV 75kV or others |
| Secondary Voltage |
33kV 13.8kV 11kV Customized |
| Frequency | 50/60Hz |
| Vector Group | Dyn11, YNd1, Dyn1, YNd11 or others |
| Winding Material | Aluminum/Copper |
| Efficiency | As IEEE, CAS Std or Customized |
| Impedance Voltage | As IEC |
| Altitude | ≤1,000m or Customized |
| Enclosure material | Mid Steel |
| HV Bushing |
| LV Bushing |
| OLTC/NLTC |
| Lifting hook for complete transformer |
| Name plate |
| Oil temperature |
| Winding temperature |
| Radiators |
| Oil level |
| Pressure relief valve |
| CT |
Customization Optional
Packing and Shipping
All 75 kV porcelain bushings, neutral bushing, conservator (if fitted), detachable radiators, OLTC drive mechanism, cooling fans, Buchholz relay, oil level indicator, temperature gauges, sudden pressure relay, and marshalling box are carefully dismantled by senior technicians. Each component is wrapped in VCI film, placed in custom IPPC-fumigated marine-plywood crates lined with ≥60 mm high-density anti-shock foam, and packed with 300 kg color-indicating silica-gel desiccant. Four 3-axis shock recorders (±250 g) and two electronic tilt indicators are fixed to every crate. Crates are clearly labeled in English/Chinese with part number, transformer serial number, gross/net weight, and “Extremely Fragile – This Side Up” warnings.
The main tank (gross weight approx. 17–21 tons) is welded onto a DNV 2.7-1 certified heavy-lift steel skid with 16 certified lashing points and four 100-ton lifting lugs. The entire body is enclosed in a fully sealed composite crate constructed from 28 mm marine plywood reinforced with 100×100 mm galvanized steel beams, then triple-wrapped with aluminum-foil vapor barrier and heavy-duty heat-sealed tarpaulin. Ten high-resolution digital impact recorders (trigger >3 g) and real-time GPS/4G tilt & vibration monitors are permanently attached. External surfaces are painted bright yellow with permanent stenciling: “75kV 1250kVA Three Phase Oil Immersed Power Transformer Copper – Gross Weight 21 Tons – Do Not Roll – Keep Dry – Use Spreader Beam Only”.
Inland transport uses low-bed or hydraulic axle trailers (total height ≤4.5 m). Sea freight is performed as break-bulk under-deck or on 40 ft heavy-duty flat-rack containers with CCS/DNV-GL approved lashing using Φ28 mm steel wire ropes and 80-ton turnbuckles. Complete documentation includes a detailed packing list, IPPC fumigation certificate, certificate of origin (Form A/E), nitrogen pressure & trend report, shock recorder baseline data, 110 % all-risk marine insurance, third-party loading survey report, and full installation manual. These rigorous measures ensure every unit arrives worldwide in perfect, ready-to-energize condition with zero damage and full traceability.
Manufacturer Test
Progress test
During manufacturing, the transformer undergoes strict staged Progress Tests with client-witness option:
- Core-coil stage: winding DC resistance at all taps, insulation resistance & PI ≥ 2.5, core grounding current <80 mA, preliminary no-load loss check.
- Pre-tanking: voltage ratio at principal and extreme taps (deviation ≤ ±0.5 %), vector group verification (Dyn11/YNd11), polarity, and magnetic balance test.
- After vapor-phase drying & vacuum oil filling: final insulation resistance (>15,000 MΩ), tanδ ≤ 0.004 (20 °C), partial discharge <10 pC at 1.5Um/√3, oil BDV ≥ 72 kV/2.5 mm, moisture <10 ppm.
- Final sealing: 48-hour static leakage test, 0.4 bar positive/negative pressure test for 24 h each, OLTC contact resistance, and mechanical operation (if applicable).
All results are fully recorded and submitted for client/third-party approval before proceeding to FAT, ensuring flawless quality.
Design Tests
All transformers will be tested after finishing the production test items as below:
♦ Leak testing with pressure for liquid-immersed transformers
♦ Test of transformer oil
♦ Measurement of voltage ratio and check of phase displacement
♦ Measurement of winding DC resistance
♦ Measurement of d. c. Insulation resistance between each winding to earth, and check of the core and frame insulation
♦ Capacitive bushing test
♦ Measurement of dissipation factor (tan δ) of the insulation system capacitances, and determination of capacitances windings-to-earth
♦ Measurement of no-load loss and current at 90%,100%,110% of rated voltage
♦ Operation test on on-load tap-changer
♦ Measurement of short-circuit impedance and load loss
♦ Lightning impulse test
♦ Induced-voltage test with partial discharge measurement
♦ Auxiliary wiring check
♦ Current transformer test
♦ Frequency response analysis test
Transformer Factory Acceptance Test
FAT is performed strictly per IEC 60076 with full client/third-party witness and signed protocol:
- Winding resistance at all taps (corrected to 75 °C)
- Voltage ratio & polarity at principal/extreme taps (≤ ±0.5 %)
- Vector group (Dyn11/YNd11) and magnetic balance
- No-load loss & current at 90 %, 100 %, 110 % rated voltage
- Load loss and impedance at 75 °C/rated current
- Separate-source & induced withstand voltage with PD <10 pC at 1.5Um/√3
- Full-wave lightning impulse test 350 kV peak (75 kV side)
- Insulation resistance, PI ≥ 2.5, tanδ ≤ 0.004, oil BDV ≥ 72 kV
- Tap-changer 8–10 full cycles + 50 auxiliary cycles
- Cooling system, Buchholz relay, sudden pressure relay, temperature indicators function test
- Sound level measurement (≤ 58 dB)
- Final visual, painting, nameplate and nitrogen pressure inspection
The official FAT report with raw data and calibration certificates is signed, confirming 100 % readiness for immediate energization.
Routine Test - No Load Loss Test
Voltage source (usually 230V, 400V or customized according to customer requirements to adapt to different equipment)
Power analyzer (used to measure power loss and efficiency)
Ammeter and voltmeter
Temperature and humidity meter
Please ensure that the test is carried out in a suitable environment with a relative humidity of less than 75% and avoid rainy days or extreme weather (recommended temperature range: 20-30°C).
Connect the test equipment to the high voltage side of the transformer, making sure the wiring is correct and the equipment is grounded.
Apply Test Voltage:
Usually it is 110% of the rated voltage, for example, if the rated voltage of the transformer is 33 KV, apply 36.3 KV (110%).
No Load Current
No Load Loss
Power Factor
Current
Voltage
Temperature and Humidity
No-load loss < 0.2% ≤ 0.5% rated power (good)
No-load loss > 0.5% rated power (further inspection or corrective action required)
Application
Technical Advantages
Product Packaging
Related Products
FAQ From Customers
-
What is a Transformer?A transformer is an electrical device used to change the voltage of alternating current (AC). It works on the principle of electromagnetic induction, converting high-voltage current into low-voltage current or low-voltage current into high-voltage current. Transformers are widely used in power transmission, distribution systems, and various electronic devices.
-
What are the main uses of a transformer?The main use of a transformer is voltage conversion. Transformers are used in power transmission systems to help transfer electricity from power plants to consumers. In addition, transformers are also used in electronic devices such as chargers, televisions, power adapters, etc., to adjust the voltage to meet the requirements of different devices.
-
Do you have UL listed?Yes, our transformer has UL listed. We have exported to America many pad mounted transformer,substation transformer and HV.