25kV 3-Layer AAAC/ACSR/AAC Tree Wire
25kV 3-Layer AAAC/ACSR/AAC Tree Wire

25kV 3-Layer AAAC/ACSR/AAC Tree Wire - Triple Layer Covered MV Conductor

The 3-Layer 25kV AAAC/ACSR/AAC Tree Wire is a specialized covered medium-voltage overhead conductor developed for distribution lines in areas with dense vegetation. It uses concentrically stranded AAAC, ACSR, or AAC conductors protected by a triple-layer system of track-resistant HDPE or XLPE. The multi-layer covering delivers exceptional tracking resistance, abrasion protection, and weatherability while greatly reducing the risk of electrical faults from tree limb contact and helping minimize wildfire ignition potential. This advanced design allows closer spacing to vegetation and lowers vegetation management costs. Suitable for conventional overhead or spacer cable systems, the 3-Layer 25kV AAAC/ACSR/AAC Tree Wire offers a cost-effective solution for improving line reliability. It complies with ICEA and ASTM standards and undergoes extensive quality testing to ensure long-term performance and safety.
Standards ICEA S-121-733, ASTM B230/B231/B232/B398/B399
Voltage Rating 25 kV
Conductor AAAC, ACSR, or AAC (concentrically stranded)
Short-Circuit Tem 250°C
Operating Temp 90°C continuous
Emergency Temp 130°C
Construction
Technical Specifications
Quality Control
Application

Construction

25kV 3-Layer AAAC/ACSR/AAC Tree Wire Constrution
25kV 3-Layer AAAC/ACSR/AAC Tree Wire

Key Product Features

Triple-layer covering system for maximum tracking resistance
AAAC, ACSR, or AAC conductor options for optimal strength
Significantly reduced fault risk from vegetation contact
Lower maintenance and wildfire mitigation benefits
Compatible with spacer cable configurations

Covering

3-Layer HDPE or XLPE

Insulation Level

100% or 133%

Covering Thickness

Triple layer (225 mils total typical)

Configuration

Single covered conductor

Technical Specifications

25kV 3-Layer AAAC/ACSR/AAC Tree Wire - Triple Layer Covered MV Conductor
25kV 3-Layer ACSR Tree Wire Data Sheet
25kV 3-Layer AAAC Tree Wire Data Sheet
25kV 3-Layer AAC Tree Wire Data Sheet
Size (AWG or kcmil) Stranding Conductor Diameter (mils) Covering Thickness (mils) Cable O.D. (mils) Rated Strength (lbs) Weight per 1000 ft.(lbs)
Conductor Shield Inner Layer Outer Layer
1/0 6/1 398 15 125 125 928 4161 385
2/0 6/1 447 15 125 125 977 5045 443
3/0 6/1 502 15 125 125 1032 6289 513
4/0 6/1 563 15 125 125 1093 7933 600
266.8 18/1 609 15 125 125 1139 6536 608
266.8 26/7 642 15 125 125 1172 10735 692
336.4 18/1 684 15 125 125 1214 8246 714
336.4 26/7 720 15 125 125 1250 13395 818
336.4 30/7 741 15 125 125 1271 16435 1086
397.5 18/1 743 15 125 125 1273 9443 804
397.5 24/7 772 15 125 125 1302 13870 863
397.5 26/7 783 15 125 125 1313 15485 926
477 24/7 846 20 125 125 1386 16340 999
477 26/7 858 20 125 125 1398 18525 1076
477 30/7 883 20 125 125 1423 22610 1458
556.5 18/1 879 20 125 125 1419 13015 1045
556.5 24/7 914 20 125 125 1454 18810 1124
556.5 26/7 927 20 125 125 1467 21470 1213
Size (kcmil) Equivalent AAC (AWG or kcmil) Stranding Conductor Diameter (mils) Covering Thickness (mils) Cable O.D. (mils) Rated Strength (lbs) Weight per 1000 ft.(lbs)
Conductor Shield Inner Layer Outer Layer
48.69 4 7 250 15 125 125 780 1584 225
77.47 2 7 316 15 125 125 846 2520 275
123.3 1/0 7 398 15 125 125 928 4014 348
155.4 2/0 7 447 15 125 125 977 4851 396
195.7 3/0 7 502 15 125 125 1032 6111 454
246.9 4/0 7 563 15 125 125 1093 7704 525
312.8 266.8 19 642 15 125 125 1172 9900 611
394.5 336.4 19 720 15 125 125 1251 11970 716
465.4 397.5 19 783 15 125 125 1313 14040 805
559.5 477 19 858 20 125 125 1398 16920 932
652.4 556.5 19 927 20 125 125 1467 19710 1044
740.8 636 37 990 20 125 125 1530 21960 1148
927.2 795 37 1108 20 125 125 1648 27450 1389
 
Size (AWG or kcmil) Stranding Conductor Diameter (mils) Covering Thickness (mils) Cable O.D. (mils) Rated Strength (lbs) Weight per 1000 ft.(lbs)
Conductor Shield Inner Layer Outer Layer
1/0 7 336 15 125 125 866 1791 309
2/0 7 376 15 125 125 906 2259 350
3/0 7 423 15 125 125 953 2736 400
4/0 7 475 15 125 125 1005 3447 460
266.8 19 537 15 125 125 1067 4473 531
336.4 19 603 15 125 125 1133 5535 621
397.5 19 659 15 125 125 1189 6399 698
477 19 722 20 125 125 1262 7524 806
556.5 37 780 20 125 125 1320 8946 899
636 37 835 20 125 125 1375 10260 995
795 37 932 20 125 125 1472 12510 1181

Quality Control

25kV 3-Layer AAAC/ACSR/AAC Tree Wire - Triple Layer Covered MV Conductor
Raw Material Test

Raw Material Test

Raw Material Test for the 3-Layer 25kV AAAC/ACSR/AAC Tree Wire involves rigorous evaluation of conductor materials and covering compounds. Chemical analysis confirms aluminum purity and alloy composition (for AAAC/AAC) or steel/aluminum for ACSR. Mechanical properties such as tensile strength, elongation, and hardness are tested to meet ASTM requirements. HDPE or XLPE compounds undergo thermal stability, tracking resistance, dielectric strength, and weatherability testing. Detailed surface and dimensional inspections identify any potential defects before processing. Only fully compliant raw materials are released for stranding and triple-layer extrusion in the production of the 3-Layer 25kV AAAC/ACSR/AAC Tree Wire. This comprehensive raw material validation establishes the foundation for superior electrical performance, mechanical strength, and long-term reliability in multi-layer tree wire applications.

 

Process inspection

Process inspection

Process Inspection throughout manufacturing of the 3-Layer 25kV AAAC/ACSR/AAC Tree Wire focuses on precision and consistency. Conductor stranding is monitored to achieve exact dimensions with continuous quality checks. Triple tandem or sequential extrusion of the three covering layers ensures clean interfaces and uniform thickness. Concentric application of layers uses automated tension control for even coverage. Jacket parameters are strictly controlled for proper thickness and adhesion. Frequent in-line diameter measurements and visual inspections catch anomalies immediately. Environmental and process variables are logged to prevent contamination. Intermediate samples undergo partial discharge and mechanical spot testing. Any non-conformance prompts swift corrective measures. These detailed process controls protect the integrity and performance characteristics of the 3-Layer 25kV AAAC/ACSR/AAC Tree Wire, resulting in a uniform, high-quality covered tree wire.

 

Finished Product

Finished Product

Every completed reel of 3-Layer 25kV AAAC/ACSR/AAC Tree Wire passes comprehensive Finished Product testing. Dimensional inspections verify overall diameter, covering thickness, and conductor stranding. DC resistance, high-voltage AC, and partial discharge tests confirm compliance with ICEA and ASTM standards. Mechanical tests measure tensile strength and elongation properties. Tracking and weathering resistance tests are performed on covering samples. Full visual examination ensures a smooth, defect-free surface with uniform layers. All tests adhere strictly to applicable standards, with complete documentation and batch traceability maintained. Packaging and labeling are inspected for accuracy. Only the 3-Layer 25kV AAAC/ACSR/AAC Tree Wire that meets every quality criterion receives final approval. This final assurance stage guarantees customers a premium triple-layer tree wire with proven dielectric strength, tracking resistance, and durability for reliable overhead distribution in vegetated areas.

 

Application

The 3-Layer 25kV AAAC/ACSR/AAC Tree Wire is perfect for overhead distribution lines in forested, suburban, or urban areas with heavy tree growth, spacer cable systems, and reconductoring projects where reduced tree trimming and improved reliability are required.

Technical Advantages

● 30+ years of manufacturing experience
● ISO and UL certified production
● Customized cable and transformer solutions

Product Packaging

Wires and Cables packaging (1)
Wires and Cables packaging (1)
Wires and Cables packaging (2)
Wires and Cables packaging (2)
Wires and Cables packaging (3)
Wires and Cables packaging (3)
Wires and Cables packaging (4)
Wires and Cables packaging (4)
Wires and Cables packaging (5)
Wires and Cables packaging (5)
Wires and Cables packaging (6)
Wires and Cables packaging (6)
Wires and Cables packaging (7)
Wires and Cables packaging (7)
Wires and Cables packaging (8)
Wires and Cables packaging (8)

Related Products

FAQ From Customers

What are the advantages of power cables and overhead lines?
(1) Reliable operation, because it is installed in a hidden place such as underground, it is less damaged by external forces, has less chance of failure, and the power supply is safe, and it will not cause harm to people;
(2) The maintenance workload is small and frequent inspections are not required;
(3) No need to erect towers;
(4) Help improve power factor.
Which aspects should be considered when choosing the cross section of a power cable?
(1) The long-term allowable working current of the cable;
(2) Thermal stability once short circuited;
(3) The voltage drop on the line cannot exceed the allowable working range.
What are the measures for cable fire prevention?
(1) Use flame-retardant cables;
(2) Use fireproof cable tray;
(3) Use fireproof paint;
(4) Fire partition walls and fire baffles are installed at cable tunnels, mezzanine exits, etc.;
(5) Overhead cables should avoid oil pipelines and explosion-proof doors, otherwise local pipes or heat insulation and fire prevention measures should be taken.
What should be paid attention to during the transportation and handling of cables?
(1) During transportation, loading and unloading, cables and cable reels should not be damaged. It is strictly forbidden to push the cable reels directly from the vehicle. Generally, cables should not be transported and stored flat.
(2) Before transporting or rolling the cable reel, ensure that the cable reel is firm, the cable is wound tightly, the oil pipe between the oil-filled cable and the pressure oil tank should be fixed without damage, the pressure oil tank should be firm, and the pressure indication should meet the requirements.
What inspections should be carried out for the acceptance of cable lines?
(1) The cable specifications should meet the regulations, the arrangement should be neat, no damage, and the signs should be complete, correct and clear;
(2) The fixed bending radius of the cable, the related distance and the wiring of the metal sheath of the single-core power cable should meet the requirements;
(3) The cable terminal and the middle head should not leak oil, and the installation should be firm. The oil pressure of the oil-filled cable and the meter setting should meet the requirements;
(4) Good grounding;
(5) The color of the cable terminal is correct, and the metal parts such as the bracket are completely painted;
(6) There should be no debris in the cable trench, tunnel, and bridge, and the cover should be complete.