2 Shrimp Aluminum Conductor Triplex Overhead Service Drop Cable
Construction
Standard
• ASTM B-231 Aluminum Conductors, Concentric-Lay-Stranded.
• ASTM B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
• ASTM B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
• ICEA S-76-474-Neutral-supported Power Cable Assemblies With Weather-Resistant Extruded Insulation Rated 600 Volts.
Phase Conductor
Neutral (Messenger) Conductor
Insulation
Key Features
2. Temperature rating: 75°C (PE), 90°C (XLP)
3. Phase Conductors: Stranded or Compressed 1350-H19 Aluminum
4. Bare AAAC messenger for neutral and support
5. Insulation: Black cross-linked polyethylene (XLP), UV and weather resistant
6. Flexible design for easy stringing and tensioning
Application
Technical Specifications
| Rated voltage | V | 600 |
| Test voltage | Veff kV/Hz | 4/50 |
| Laying temperature | °C | min. -5 |
| Operating temperature | °C | -30 ~ +90 |
| Conductor temperature | °C | max. +90 |
| Short-circuit temperature | °C/s | max. +250 /5 |
| Bending radius (min.) | mm | 20 × Ø of cable |
Quality Control
Raw Material Test
Incoming materials for 2-2-2 Shrimp Aluminum Conductor Triplex Overhead Service Drop Cable pass strict verification. 1. 1350-H19 aluminum rods tested for purity, conductivity (>61% IACS), tensile, and elongation per ASTM B-230/B-233. 2. Neutral messenger (ACSR/AAAC) components verified for galvanization, tensile strength (B-232/B-498), or alloy specs (B-399). 3. XLPE pellets checked for melt index, density, aging performance, tensile/elongation, and UV stabilizers. 4. Supplier documentation reviewed with random sampling for defects. Rejected lots returned; approved materials tagged for traceability.
Process inspection
In-process quality for 2-2-2 Shrimp Aluminum Conductor Triplex Overhead Service Drop Cable maintains precision. 1. Stranding monitored for accurate lay, strand count, and no overlaps in #2 AWG conductors/neutral. 2. Insulation extrusion: XLPE thickness gauged continuously (nominal 0.045 inches), parameters logged for cross-linking. 3. Twisting: Triplex assembly verified for balance, lay length, and insulation protection. 4. Inline spark testing detects faults. 5. Regular sampling for resistance, visual defects, and dimensions. Non-conformances trigger corrections and segregation.
Finished Product
Final QA on 2-2-2 Shrimp Aluminum Conductor Triplex Overhead Service Drop Cable confirms standards. 1. Conductor DC resistance/stranding per ASTM. 2. Insulation resistance/AC withstand (no flashover). 3. Physical: Thickness, eccentricity, tensile/elongation. 4. Ampacity (~150A) validated. 5. Visual check for marking ("Shrimp", specs), surface condition. 6. Flexibility/coiling tests. Full reports generated; passing products certified, labeled, and approved for shipment.
Application
Technical Advantages
Product Packaging
Related Products
FAQ From Customers
-
What are the advantages of power cables and overhead lines?(1) Reliable operation, because it is installed in a hidden place such as underground, it is less damaged by external forces, has less chance of failure, and the power supply is safe, and it will not cause harm to people; (2) The maintenance workload is small and frequent inspections are not required; (3) No need to erect towers; (4) Help improve power factor.
-
Which aspects should be considered when choosing the cross section of a power cable?(1) The long-term allowable working current of the cable; (2) Thermal stability once short circuited; (3) The voltage drop on the line cannot exceed the allowable working range.
-
What are the measures for cable fire prevention?(1) Use flame-retardant cables; (2) Use fireproof cable tray; (3) Use fireproof paint; (4) Fire partition walls and fire baffles are installed at cable tunnels, mezzanine exits, etc.; (5) Overhead cables should avoid oil pipelines and explosion-proof doors, otherwise local pipes or heat insulation and fire prevention measures should be taken.
-
What should be paid attention to during the transportation and handling of cables?(1) During transportation, loading and unloading, cables and cable reels should not be damaged. It is strictly forbidden to push the cable reels directly from the vehicle. Generally, cables should not be transported and stored flat. (2) Before transporting or rolling the cable reel, ensure that the cable reel is firm, the cable is wound tightly, the oil pipe between the oil-filled cable and the pressure oil tank should be fixed without damage, the pressure oil tank should be firm, and the pressure indication should meet the requirements.
-
What inspections should be carried out for the acceptance of cable lines?(1) The cable specifications should meet the regulations, the arrangement should be neat, no damage, and the signs should be complete, correct and clear; (2) The fixed bending radius of the cable, the related distance and the wiring of the metal sheath of the single-core power cable should meet the requirements; (3) The cable terminal and the middle head should not leak oil, and the installation should be firm. The oil pressure of the oil-filled cable and the meter setting should meet the requirements; (4) Good grounding; (5) The color of the cable terminal is correct, and the metal parts such as the bracket are completely painted; (6) There should be no debris in the cable trench, tunnel, and bridge, and the cover should be complete.