600kVA Oil Immersed Transformer
- Primary Voltage Ratings 34.5-19.92/13.8-7.957/13.2-7.62/12.47-7.2, 24.94, 26.25, 33 or others
- Secondary Voltage Ratings 480/277V, 400/230V, 380/220V or customized
- H.V. Tap Range ± 2×2.5% HV taps or others
- Type Oil immersed distribution transformer
- BIL 30/95kV
- Standards IEEE, ANSI, NEMA, IEC, CE
- Application Temporary Power Supply Systems, Utilities
- Power Rating 600kVA
- Certificate UL, CESI, IEEE
- Cooling Method ONAN, ONAN/ONAF, KNAN, KNAN/KNAF
- Oil Mineral Oil or FR3
- Opeartion Step Down & Step Up
Technical Specifications
| Rated Power | 600kVA | |
| Rating Primary Voltage | 2.4 - 34.5kV | |
| Secondary Voltage | 480/277V 400/230V 380/220V Customized |
|
| Frequency | 50/60Hz | |
| Vector Group | Dyn11, Yyn0, Dyn5 | |
| Winding Material | Aluminum/Copper | |
| Efficiency | As IEEE, Doe 2016, CAS Std or Customized | |
| Impedance Voltage | Nominal 2% or Customized 1.1 - 5.75% | |
| Altitude | ≤1,000m or Customized | |
| Color | ANSI 70 Light gray/Munsell 7GY3.29/1.5 or customized, etc | |
| Tank material | Mild Steel, 304 Stainless Steel | |
| Insulating Oil Weight | 830kg | |
| Total Weight | 2605kg | |
| Outline Dimensions(L×W×H)in. | 1900 × 1000 × 1850(mm) | |
| HV Bushing |
| LV Bushing |
| Tap changer |
| Oil level gauge |
| Oil temperature indicator |
| Pressure relief device |
| Pressure vacuum gauge |
| Lifting hook for complete transformer |
| Name plate |
| Radiators |
| Oil upper filtering valve |
| Oil drain valve with 3/8" sampler |
Customization Optional
Packing and Shipping
Individual components are safeguarded separately: radiators are foam-padded and crated with vibration dampers, bushings in impact-resistant enclosures, and control elements sealed with desiccants. The main body mounts on sturdy ISPM-15 wooden crates or steel skids with custom bracing, lateral supports, and energy-absorbing materials rated for 4-5g forces common in logistics. Packaging features weatherproof layers, corrosion inhibitors, humidity/temperature indicators, and shock/tilt recorders for transit monitoring.
Ocean export—typical for international deliveries—employs flat-rack/open-top containers with IMO lashing, salt-fog barriers, and protective covers; road/rail uses low-bed trailers with balanced cradles and designated lift points. Full documentation includes invoices, packing lists, origin/conformity certificates, routine test reports, dimensional/lifting drawings, oil SDS, handling/installation guides, and HS codes (8504.21 for ≤650kVA distribution transformers).
We handle end-to-end logistics with FOB/CIF/door options, customs assistance, insurance, and enhanced services like third-party verifications, on-site crane unloading supervision, oil filtration/degassing, erection support, and commissioning. This comprehensive strategy prevents damage, maintains as-new condition, meets global regulations, and ensures prompt, secure delivery for distribution, commercial, and industrial clients worldwide.
Manufacturer Test
Progress Test
NPC ELECTRIC's 600kVA oil-immersed transformers insulating oil progress assesses breakdown voltage moisture acidity and purity per IEC 60296 with filtration to low contaminant levels. Core-coil drying progress tracks vacuum oven parameters and dew point below -45°C for superior insulation. Tank filling progress supervises vacuum impregnation degassing nitrogen blanketing and pressure decay leak tests. Accessory progress verifies temperature gauge calibration pressure relief operation gas relay functionality and tap changer sequencing. Pre-dispatch progress encompasses dimensional weight visual inspection labeling packaging checks shock tests and traceable photo/digital logs ensuring full compliance and dispatch readiness.
Design Tests
All transformers will be tested after finishing the production, test items as follows:
♦ Insulation Power Factor
♦ Ratio, Polarity, and Phase Relation
♦ Winding Resistance
♦ Impulse Tests
♦ On load Loss Test
♦ No Load Loss Test
♦ Leak Test
♦ DC Insulation Resistance Test
♦ Transformer Turns Ratio/TTR (All Tap Voltages)
♦ Impedance Voltage & Load Loss (Rated Voltage)
♦ Polarity, 1-Ph / Phase Relation, 3-Ph (Rated Voltage)
♦ Excitation & No-Load Loss (Rated Voltage)
♦ Insulation Resistance (Rated Voltage)
♦ Temperature Rise
♦ Dielectric Withstand (Hipot)
Transformer Factory Acceptance Test
Load loss impedance voltage efficiency tests short secondary reduced voltage compute copper losses impedance (~4.5-6%) total losses at 75°C for regulation evaluation. Oil routine checks dielectric (>55kV/2.5mm) water (<30ppm) acidity DGA baseline. Temperature rise indicators verify accuracy alarms. Functional tests include relief valve activation gas relay tripping, tap changer operation sound level (<58dB). Mechanical validation covers tank overpressure leak-free bushing coordination wiring. Comprehensive FAT reports calibration certificates optional witnessing confirm IEC 60076 compliance routine tests before shipment.
Routine Test - Polarity 1-Ph
Voltage source: usually 500 V, 1000 V or customized as needed
Environmental monitoring: Temperature and humidity meter (records ambient temperature and humidity)
Check the connection terminals and wiring to ensure that there is no looseness or contamination.
Test under suitable environmental conditions: relative humidity less than 75% and no rain (recommended temperature: 20-30°C).
Connect the test equipment to the bushing or terminal of the device under test and ensure proper grounding.
Apply Test Voltage:
Select the appropriate test voltage according to the rated voltage of the device. For single-phase systems, the applied voltage should comply with the equipment specifications (such as 220V or 380V, etc.).
Phase sequence: Confirm whether the phase sequence of the power supply is correct.
Polarity: Check whether the wiring meets the predetermined polarity (positive and negative terminals are connected correctly).
Voltage: The actual voltage value during the test.
Application
Technical Advantages
Product Packaging
Related Products
FAQ From Customers
-
What is a Transformer?A transformer is an electrical device used to change the voltage of alternating current (AC). It works on the principle of electromagnetic induction, converting high-voltage current into low-voltage current or low-voltage current into high-voltage current. Transformers are widely used in power transmission, distribution systems, and various electronic devices.
-
What are the main uses of a transformer?The main use of a transformer is voltage conversion. Transformers are used in power transmission systems to help transfer electricity from power plants to consumers. In addition, transformers are also used in electronic devices such as chargers, televisions, power adapters, etc., to adjust the voltage to meet the requirements of different devices.
-
Do you have UL listed?Yes, our transformer has UL listed. We have exported to America many pad mounted transformer,substation transformer and HV.