(N)TSCGECECWOU 8.7/15kV and 12/20kV ZH Cable
- Voltage Rating Uo/U 8.7/15kV | 12/20kV
-
Test Voltage
8.7/15kV: 24kV
12/20kV: 29kV -
Temperature Rating
Fixed: -50°C to +80°C
Flexed: -40°C to +80°C -
Minimum Bending Radius
Fixed: 6 x overall diameter
Flexed: 10 x overall diameter
Construction
Phase Conductor
Insulation
Protective Earth Conductor
Control Conductor
Central Filler
Inner Sheath
Monitoring Conductor
Outer Sheath
Sheath Colour
Manufacturer Standard
Flame Retardant
Halogen Free
Semi-Conductive Layers
semi-conductive rubber layer on the insulation
Application
Technical Specifications
|
No. Of Cores CONTROL+UL) |
Nominal Cross Sectional Area mm² |
CONDUCTOR DIAMETER |
MINIMUM OVERALL DIAMETER |
MAXIMUM OVERALL DIAMETER |
MAXIMUM TENSILE LOAD |
NOMINAL WEIGHT |
||
|
Phase N Conductor |
Earth Conductor |
Control Conductor |
mm | mm | mm | N | kg/km | |
| 3+3+3+UL | 25 | 25/3E | 2.5ST | 6.8 | 48 | 51.5 | 1125 | 3540 |
| 3+3+3+UL | 35 | 25/3E | 2.5ST | 7.8 | 49.5 | 53.1 | 1575 | 3930 |
| 3+3+3+UL | 50 | 25/3E | 2.5ST | 9.4 | 54.4 | 58.2 | 2250 | 4810 |
| 3+3+3+UL | 70 | 35/3E | 2.5ST | 11.2 | 58.2 | 62.2 | 3150 | 5880 |
| 3+3+3+UL | 95 | 50/3E | 2.5ST | 12.7 | 61.4 | 65.7 | 4275 | 6950 |
|
No. Of Cores CONTROL+UL) |
Nominal Cross Sectional Area mm² |
CONDUCTOR DIAMETER |
MINIMUM OVERALL DIAMETER |
MAXIMUM OVERALL DIAMETER |
MAXIMUM TENSILE LOAD |
NOMINAL WEIGHT |
||
|
Phase N Conductor |
Earth Conductor |
Control Conductor |
mm | mm | mm | N | kg/km | |
| 3+3+3+UL | 25 | 25/3E | 2.5ST | 6.8 | 50.5 | 54.1 | 1125 | 3800 |
| 3+3+3+UL | 35 | 25/3E | 2.5ST | 7.8 | 52.3 | 56 | 1575 | 4190 |
| 3+3+3+UL | 50 | 25/3E | 2.5ST | 9.4 | 57.5 | 61.4 | 2250 | 5120 |
| 3+3+3+UL | 70 | 35/3E | 2.5ST | 11.2 | 61 | 65.3 | 3150 | 6200 |
| 3+3+3+UL | 95 | 50/3E | 2.5ST | 12.7 | 66.4 | 70.9 | 4275 | 7550 |
Quality Control
Raw Material Test
Raw Material Test for (N)TSCGECECWOU 8.7/15kV and 12/20kV ZH Cable confirms ZH-compliant premium inputs for MV safety. The structured process includes: Supplier Certification Review: Verify class 5 tinned copper meets DIN EN 60228/IEC 60228 for purity (>99.9% Cu), stranding, and tin coating; EPR insulation, halogen-free inner sheath, and PUR outer sheath certified to VDE 0250. Conductor Analysis: Test tinned copper for tensile strength (>200 MPa), elongation (>20%), conductivity (≥97% IACS), and tin uniformity. Semi-Conductive & Insulation Testing: Semi-conductive layers checked for resistivity/adhesion; EPR insulation evaluated for tensile (>6.5 MPa), elongation (>300%), dielectric strength (>20 kV/mm), and thermal aging per IEC 60502.
Process inspection
Process Inspection during manufacturing of (N)TSCGECECWOU 8.7/15kV and 12/20kV ZH Cable maintains ZH safety and precision. Steps include: Conductor Stranding: Monitor fine class 5 stranding of phase/control/monitoring conductors for uniform lay, compactness, and flexibility. Layer Extrusion: Apply semi-conductive screens and EPR insulation at precise thicknesses; inline scanners, spark testers, and eccentricity monitors detect voids/defects. Screening & Assembly: Braid copper wires for earth/screening with controlled coverage/tension; integrate monitoring conductor. ZH Inner & Outer Sheath Extrusion: Apply halogen-free inner sheath and PUR outer sheath; real-time checks on thickness, surface finish, adhesion, and ZH properties. Continuous Monitoring: Conductor resistance, insulation integrity, screen continuity, overall diameter, and halogen-free verification throughout.
Finished Product
Finished Product Test confirms the (N)TSCGECECWOU 8.7/15kV and 12/20kV ZH Cable meets ZH/MV standards before shipment. The procedure includes: Visual & Dimensional Inspection: Examine full length for defects, uniformity, markings, and measure outer diameter/weight per meter. Electrical Tests: DC resistance, insulation resistance (>1000 MΩ·km), high-voltage withstand (24kV for 8.7/15kV, 29kV for 12/20kV/5 min), partial discharge, and screen/monitoring continuity per VDE/IEC. Mechanical Evaluation: Bending radius (typically 6–8× OD), tensile strength, abrasion, tear, and torsional resistance tested. ZH Performance: Halogen content (IEC 60754), low smoke density (IEC 61034), flame retardancy (IEC 60332), oil/chemical immersion, and thermal aging verified. Thermal & Environmental Validation: Confirm 90°C rating and resistance to moisture/mechanical stress.
Application
Technical Advantages
Product Packaging
Related Products
FAQ From Customers
-
What are the advantages of power cables and overhead lines?(1) Reliable operation, because it is installed in a hidden place such as underground, it is less damaged by external forces, has less chance of failure, and the power supply is safe, and it will not cause harm to people; (2) The maintenance workload is small and frequent inspections are not required; (3) No need to erect towers; (4) Help improve power factor.
-
Which aspects should be considered when choosing the cross section of a power cable?(1) The long-term allowable working current of the cable; (2) Thermal stability once short circuited; (3) The voltage drop on the line cannot exceed the allowable working range.
-
What are the measures for cable fire prevention?(1) Use flame-retardant cables; (2) Use fireproof cable tray; (3) Use fireproof paint; (4) Fire partition walls and fire baffles are installed at cable tunnels, mezzanine exits, etc.; (5) Overhead cables should avoid oil pipelines and explosion-proof doors, otherwise local pipes or heat insulation and fire prevention measures should be taken.
-
What should be paid attention to during the transportation and handling of cables?(1) During transportation, loading and unloading, cables and cable reels should not be damaged. It is strictly forbidden to push the cable reels directly from the vehicle. Generally, cables should not be transported and stored flat. (2) Before transporting or rolling the cable reel, ensure that the cable reel is firm, the cable is wound tightly, the oil pipe between the oil-filled cable and the pressure oil tank should be fixed without damage, the pressure oil tank should be firm, and the pressure indication should meet the requirements.
-
What inspections should be carried out for the acceptance of cable lines?(1) The cable specifications should meet the regulations, the arrangement should be neat, no damage, and the signs should be complete, correct and clear; (2) The fixed bending radius of the cable, the related distance and the wiring of the metal sheath of the single-core power cable should meet the requirements; (3) The cable terminal and the middle head should not leak oil, and the installation should be firm. The oil pressure of the oil-filled cable and the meter setting should meet the requirements; (4) Good grounding; (5) The color of the cable terminal is correct, and the metal parts such as the bracket are completely painted; (6) There should be no debris in the cable trench, tunnel, and bridge, and the cover should be complete.