40MVA 110kV Three Phase Oil Immersed Transformer for Substation
- Primary Voltage Ratings 34.5-19.92/13.8-7.957/13.2-7.62/12.47-7.2, 33 or others
- Secondary Voltage Ratings 480/277V, 400/230V, 380/220V or customized
- H.V. Tap Range ± 2×2.5% HV taps or others
- Type Oil immersed transformer
- BIL 30/95kV
- Standards IEEE, ANSI, NEMA, IEC, CE
- Application Power Substations, Industrial Power Supply
- Power Rating 40MVA
- Certificate UL, CESI, IEEE
- Cooling Method ONAN, ONAN/ONAF, KNAN, KNAN/KNAF
- Oil Mineral Oil or FR3
- Opeartion Step Down & Step Up
Technical Specifications
| Rated Power | 40 MVA | |
| Rating Primary Voltage | 2.4 - 110kV | |
| Secondary Voltage | 480/277V 400/230V 380/220V Customized |
|
| Frequency | 50/60Hz | |
| Vector Group | Dyn11, Yyn0, Dyn5 | |
| Winding Material | Aluminum/Copper | |
| Efficiency | As IEEE, Doe 2016, CAS Std or Customized | |
| Impedance Voltage | Nominal 2% or Customized 1.1 - 5.75% | |
| Altitude | ≤1,000m or Customized | |
| Color | ANSI 70 Light gray/Munsell 7GY3.29/1.5 or customized, etc | |
| Tank material | Mild Steel, 304 Stainless Steel | |
| HV Bushing |
| LV Bushing |
| Tap changer |
| Oil level gauge |
| Oil temperature indicator |
| Pressure relief device |
| Pressure vacuum gauge |
| Lifting hook for complete transformer |
| Name plate |
| Radiators |
| Oil upper filtering valve |
| Oil drain valve with 3/8" sampler |
Customization Optional
Packing and Shipping
After FAT approval, the transformer is vacuum-dehydrated and filled with dry nitrogen to 0.03–0.04 MPa positive pressure to prevent moisture ingress. All 110kV porcelain bushings, conservator, radiator banks, OLTC diverter, cooling fans, Buchholz relay, and instruments are dismantled and packed in separate IPPC-fumigated plywood crates with high-density foam and desiccant. The main tank is fixed on a heavy-duty steel skid with certified lifting and lashing points, then fully enclosed in a reinforced 25 mm marine plywood crate wrapped in a double-layer waterproof and aluminum-foil barrier. Clear bilingual markings (“40MVA 110kV Three Phase Oil Immersed Transformer”), weight (~70 tons), center-of-gravity, lifting points, and handling instructions are applied. Eight shock recorders and tilt indicators monitor the entire journey.
For shipping, inland transport uses police-escorted hydraulic modular trailers (height ≤5.0 m). Sea freight is break-bulk under-deck or on DNV-certified 40ft/80ft flat-racks secured with Φ32 mm wire ropes and pre-approved lashing plans. Full documentation—including packing list, origin certificate, fumigation certificate, nitrogen report, and 110% insurance—is provided. These measures guarantee every 40MVA 110kV Three Phase Oil Immersed Transformer reaches the site ready for immediate installation and commissioning.
Manufacturer Test
Progress Test
During manufacturing, the 40MVA 110kV Three Phase Oil Immersed Transformer undergoes strict staged Progress Tests per IEC 60076:
- Core-coil assembly: winding DC resistance at all taps, insulation resistance (PI ≥ 2.5), core grounding current (<100 mA), and preliminary no-load loss check.
- Pre-tanking: voltage ratio at principal/extreme taps (deviation ≤ ±0.5%), vector group confirmation (YNd11/Dyn11), polarity, and winding power factor.
- After vapor-phase drying & vacuum oil-filling: final insulation resistance, tanδ (≤ 0.0035 at 20℃), partial discharge (<10 pC at 1.5Um/√3), and oil dielectric strength (>70 kV/2.5 mm).
- Tank sealing: 24-hour static leakage test and 0.4 bar positive/negative pressure test for 24 h.
All results are recorded and submitted for client/third-party approval before final FAT, ensuring the 40MVA 110kV Three Phase Oil Immersed Transformer fully meets design and quality requirements.
Design Tests
All transformer will be test after finished the production, test items as below:
♦ Insulation Power Factor
♦ Ratio, Polarity, and Phase Relation
♦ Winding Resistance
♦ Impulse Tests
♦ On load Loss Test
♦ No Load Loss Test
♦ Leak Test
♦ DC Insulation Resistance Test
♦ Transformer Turns Ratio/TTR (All Tap Voltages)
♦ Impedance Voltage & Load Loss (Rated Voltage)
♦ Polarity, 1-Ph / Phase Relation, 3-Ph (Rated Voltage)
♦ Excitation & No-Load Loss (Rated Voltage)
♦ Applied Voltage
♦ Induced Voltage
♦ Lightning Impulse
♦ Insulation Resistance (Rated Voltage)
♦ Temperature Rise
♦ Dielectric Withstand (Hipot)
Transformer Factory Acceptance Test
Conducted strictly per IEC 60076-1/3/11 with client or third-party (SGS/BV/TÜV) witness:
- Winding resistance measurement at all tap positions
- Voltage ratio & phase displacement at principal tap and ± extreme taps (deviation ≤ ±0.5%)
- Vector group and polarity verification (typically YNd11 or Dyn11)
- No-load loss and no-load current at 90%, 100%, and 110% rated voltage
- Load loss and short-circuit impedance at 75℃ and rated current
- Separate-source applied voltage withstand test
- Induced overvoltage withstand test with PD measurement (<10 pC at 1.5Um/√3, <5 pC at Um/√3)
- Full-wave lightning impulse test 350–400 kV peak (HV) & 170–200 kV (MV)
- Insulation resistance, polarization index (PI ≥ 2.5), tanδ, capacitance, and oil BDV (>70 kV)
Official FAT protocol signed upon acceptance, confirming the 40MVA 110kV Three Phase Oil Immersed Transformer is fully qualified for 110kV substation and power plant service.
Routine Test - Winding Resistance
Test voltage source (commonly used are 6V, 10V, 20V, 40V or 100V, depending on the equipment model or customer requirements)
Temperature and humidity meter (used to record the ambient temperature and humidity during the test)
Disconnect the electrical connection between the test cable and the equipment to ensure that there is no external current or voltage interference.
Select a suitable voltage range for testing and set the test voltage according to the equipment requirements.
Connect the test equipment to the winding terminals of the device under test, making sure the connections are secure and properly grounded to avoid measurement errors.
Apply Test Voltage:
Select the appropriate test current according to the equipment specifications (such as test current for low-voltage windings, single-phase or three-phase windings).
Winding resistance (usually expressed in units of "Ω")
Test current (A)
Test voltage (V)
Temperature (record the winding temperature before and after the test)
Resistance deviation is between 5% and 10% (warning)
Resistance deviation exceeds 10% (further inspection or corrective action is required)
Application
Technical Advantages
Product Packaging
Related Products
FAQ From Customers
-
What is a Transformer?A transformer is an electrical device used to change the voltage of alternating current (AC). It works on the principle of electromagnetic induction, converting high-voltage current into low-voltage current or low-voltage current into high-voltage current. Transformers are widely used in power transmission, distribution systems, and various electronic devices.
-
What are the main uses of a transformer?The main use of a transformer is voltage conversion. Transformers are used in power transmission systems to help transfer electricity from power plants to consumers. In addition, transformers are also used in electronic devices such as chargers, televisions, power adapters, etc., to adjust the voltage to meet the requirements of different devices.
-
Do you have UL listed?Yes, our transformer has UL listed. We have exported to America many pad mounted transformer,substation transformer and HV.