x
Oil-Immersed Copper Power Transformer 1
Oil-Immersed Copper Power Transformer 2
Oil-Immersed Copper Power Transformer 3
Oil-Immersed Copper Power Transformer 4
Oil-Immersed Copper Power Transformer 1
Oil-Immersed Copper Power Transformer 2
Oil-Immersed Copper Power Transformer 3
Oil-Immersed Copper Power Transformer 4

20kV Three-Phase Oil-Immersed Power Transformer 50-2500kVA Copper

The 20kV Three-Phase Oil-Immersed Power Transformer 50-2500kVA Copper adopts high-purity electrolytic copper windings, Class A insulation, and advanced ONAN cooling design. Available in energy-saving S11/S13/S20 series with no-load loss reduced by up to 40%. Fully sealed corrugated tank or conservator type effectively prevents oil aging and moisture ingress. It complies with IEC 60076, GB/T 1094, and can be equipped with ±5% or ±2×2.5% off-circuit tap changer. Low noise (<55 dB), strong short-circuit withstand capability, and overload capacity make it ideal for industrial parks, commercial buildings, and renewable energy projects. Vacuum oil filling and nitrogen sealing ensure insulation performance for over 30 years. Factory supports full third-party inspection (SGS/BV) and provides type test reports.
Primary Voltage Ratings 35kV, 34.5kV, 33kV, 46kV or others
Secondary Voltage Ratings 13.8kV 6kV 10kV or others
H.V. Tap Range ±8×1.25% or others
Type Oil-immersed power transformer
BIL 20kV
Standards IEEE, ANSI, NEMA, IEC, CE
Application industrial distribution networks, large factories
Power Rating 50-2500kVA
Certificate UL, CESI, IEEE
Cooling Method ONAN/ONAF
Oil Mineral Oil or FR3
Opeartion Step Down & Step Up
Technical Specifications
Customization Optional
Packing and Shipping
Manufacturer Test
Routine Testing
Application

Technical Specifications

20kV Three-Phase Oil-Immersed Power Transformer 50-2500kVA Copper
Technical Specifications
Accessories
Rated Power 50-2500kVA
Rating Primary Voltage 20 kV
Secondary Voltage

6.6kV

10kV

13.8kV

Customized

Frequency 50/60Hz
Vector Group Dyn11, Yyn0, Dyn5
Winding Material Aluminum/Copper
Efficiency As IEEE, Doe 2016, CAS Std or Customized
Impedance Voltage Nominal 2% or Customized 1.1 - 5.75% 
Altitude ≤1,000m or Customized
Color ANSI 70 Light gray/Munsell 7GY3.29/1.5 or customized, etc
Tank material Mild Steel, 304 Stainless Steel
HV Bushing
LV Bushing
Tap changer
Oil level gauge
Oil temperature indicator
Pressure relief device
Pressure vacuum gauge
Lifting hook for complete transformer
Name plate
Radiators
Oil upper filtering valve
Oil drain valve with 3/8" sampler

Customization Optional

20kV Three-Phase Oil-Immersed Power Transformer 50-2500kVA Copper
Clients can freely select capacity 50-2500kVA, copper or aluminum windings, S11/S13/S20 low-loss series, voltage ratios 20±5%/0.4kV, 20/0.69kV, 20/10.5kV or special dual-voltage. Tap changer options include off-circuit ±2×2.5%, ±5% or on-load ±8×1.25%. Vector group Dyn11, Yyn0, or custom. Cooling methods: ONAN or ONAF with auto fan control. Tank types: corrugated fins, detachable radiator, or fully sealed conservator.
Additional options include built-in protection (gas relay, pressure relief valve, oil temperature/winding temperature gauge with 4-20mA output), IP54 protective enclosure, anti-corrosion C5-M painting, high-altitude (>3000 m) design, low-noise version (<50 dB), online oil filtration interface, and smart monitoring terminal for SCADA. All customizations fully comply with IEC standards and support type/special test reports.

Packing and Shipping

20kV Three-Phase Oil-Immersed Power Transformer 50-2500kVA Copper
After FAT approval, the 20kV transformer is vacuum dried and filled with dry nitrogen to 0.02-0.03 MPa to prevent oil oxidation during long-distance transport.
All bushings, oil level gauge, temperature gauges, and tap changer handle are dismantled and packed in separate IPPC-fumigated wooden crates with shock-proof foam and desiccant. The main body is fixed on a reinforced steel skid, wrapped with waterproof film, and placed in a fully sealed plywood crate reinforced with a 50×50 mm steel frame. Clear bilingual markings “20kV Three-Phase Oil-Immersed Power Transformer 50-2500kVA Copper”, lifting points, centre-of-gravity, and “Keep Dry” are applied. Four shock recorders monitor the entire journey.
Land transport uses standard low-bed trailers (height <4.3 m). Sea freight is loaded in 40ft OT/FR containers or break-bulk, secured with certified lashing belts. Complete documentation includes a packing list, fumigation certificate, nitrogen pressure report, and 110% marine insurance.
These professional measures ensure every unit arrives in perfect condition, ready for immediate installation and commissioning worldwide.
Oil Immersed Power Transformer package
Oil Immersed Power Transformer package mini
32
32 years of industry experience

Manufacturer Test

20kV Three-Phase Oil-Immersed Power Transformer 50-2500kVA Copper
Oil Immersed Power Transformer Progress Test

Progress Test

During production, the 20kV Three-Phase Oil-Immersed Power Transformer undergoes strict staged Progress Tests:

  1. Core-coil: winding DC resistance at all taps, insulation resistance (PI ≥ 2.0), core grounding current <50 mA.
  2. Pre-tanking: ratio at all taps (deviation ≤ ±0.5%), vector group Dyn11/Yyn0 verification.
  3. After vapor-phase drying & vacuum oil-filling: final insulation resistance, tanδ ≤ 0.004, PD <5 pC at 1.5Um/√3, oil BDV >60 kV.
  4. Tank sealing: 24 h leakage test + 0.3 bar pressure/vacuum test. All records are submitted for client approval before FAT. 
Oil Immersed Power Transformer  Design Tests

Design Tests

All transformer will be test after finished the production, test items as below:
♦ Insulation Power Factor
♦ Ratio, Polarity, and Phase Relation
♦ Winding Resistance
♦ Impulse Tests
♦ On load Loss Test
♦ No Load Loss Test
♦ Leak Test
♦ DC Insulation Resistance Test
♦ Transformer Turns Ratio/TTR (All Tap Voltages)
♦ Impedance Voltage & Load Loss (Rated Voltage)
♦ Polarity, 1-Ph / Phase Relation, 3-Ph (Rated Voltage)
♦ Excitation & No-Load Loss (Rated Voltage)
♦ Applied Voltage
♦ Induced Voltage
♦ Lightning Impulse
♦ Insulation Resistance (Rated Voltage)
♦ Temperature Rise
♦ Dielectric Withstand (Hipot)

China NPC ELECTRIC

Transformer Factory Acceptance Test

The Factory Acceptance Test is performed strictly in accordance with IEC 60076-1/3/5/11, GB/T 1094, and customer technical specifications, fully witnessed by the client or third-party inspection agency (SGS, BV, TÜV, etc.).

  1. Winding resistance measurement at all tap positions (ambient temperature, corrected to 75 °C)
  2. Voltage ratio and polarity test at rated tap and all off-circuit/on-load tap positions (tolerance ≤ ±0.5 %)
  3. Vector group and magnetic balance verification (typically Dyn11 or Yyn0)
  4. No-load loss and no-load current at 90 %, 100 %, and 110 % rated voltage on principal tap

All raw data, oscillograms, and calibration certificates are recorded in the official FAT protocol. The transformer is released for shipment only after client signature, ensuring every 20kV Three-Phase Oil-Immersed Power Transformer 50-2500kVA Copper is 100 % qualified for immediate energization and long-term reliable service.

Routine Test - Applied Voltage

Purpose of Testing
The purpose of testing the applied voltage is to verify the insulation strength of the transformer by applying a voltage higher than its normal operating level, ensuring it can withstand potential electrical stresses. This test helps identify any weaknesses or defects in the insulation system before the transformer is put into service.
Testing Equipment
Test equipment: High voltage tester (e.g. TTR, Hipot, etc.)
Voltage source: usually 1 kV, 5 kV, 10 kV, or customized according to customer needs
Temperature and humidity meter: used to record environmental conditions
Pre-Test Preparation
Disconnect the device from the power supply and make sure it is properly grounded and discharged.
Check the connection terminals and wiring to ensure that they are not loose or contaminated.
Test under suitable environmental conditions: relative humidity below 75% and no rain (recommended temperature: 20-30°C).
Test Progress
Connect the Test Instrument:
Properly connect the test equipment to the bushings or terminals of the device under test and ensure that all connection points are properly grounded.
Selecting the test voltage:
Select the appropriate applied voltage based on the rated voltage of the equipment.
Measure and Record
Start the test and record the following parameters:
Measuring leakage current
Applied voltage
Current stability
Any possible voltage fluctuations
Temperature Correction
If necessary, the measured data is temperature corrected to ensure that it corresponds to standard temperature conditions (usually 20°C).
Repeat Testing (if necessary)
Multiple tests were conducted on different windings (high voltage, medium voltage, low voltage) and bushings, and comparative analysis was performed.
Evaluation Criteria (Reference)
The test was normal and the equipment performed well (qualified)
The current value exceeded the allowable range and the equipment needs to be inspected or maintained (pending repair)
There was a serious fault or instability and the equipment could not continue to operate (unqualified)
Observing electrical behavior
Observe the electrical behavior of the device under test to ensure that there are no abnormal currents, arcing, noise, or electrical faults.
*These comprehensive tests ensure that each transformer meets performance standards and operates reliably under various conditions.
Oil Immersed Transformer Routine Test

Application

Widely used in 20kV industrial distribution networks, large factories (chemical, steel, paper), commercial complexes, data centers, hospitals, urban compact substations, wind/solar farm step-up stations, port & railway 20kV power supply systems, and rural 35kV/20kV transformation projects.

Technical Advantages

● 30+ years of manufacturing experience
● ISO and UL certified production
● Customized cable and transformer solutions

Product Packaging

Transformers Packaging (1)
Transformers Packaging (1)
Transformers Packaging (2)
Transformers Packaging (2)
Transformers Packaging (3)
Transformers Packaging (3)
Transformers Packaging (4)
Transformers Packaging (4)
Transformers Packaging (5)
Transformers Packaging (5)
Transformers Packaging (6)
Transformers Packaging (6)
Transformers Packaging (7)
Transformers Packaging (7)
Transformers Packaging (8)
Transformers Packaging (8)

Related Products

FAQ From Customers

What is a Transformer?
A transformer is an electrical device used to change the voltage of alternating current (AC). It works on the principle of electromagnetic induction, converting high-voltage current into low-voltage current or low-voltage current into high-voltage current. Transformers are widely used in power transmission, distribution systems, and various electronic devices.
What are the main uses of a transformer?
The main use of a transformer is voltage conversion. Transformers are used in power transmission systems to help transfer electricity from power plants to consumers. In addition, transformers are also used in electronic devices such as chargers, televisions, power adapters, etc., to adjust the voltage to meet the requirements of different devices.
Do you have UL listed?
Yes, our transformer has UL listed. We have exported to America many pad mounted transformer,substation transformer and HV.

Welcome your inquiry

Honesty, Integrity, Frugality, Activeness and Passion